g a separate discrete light emitting indicator
and/or a field on the alphanumeric display
shall be visible when a fire signal is
received and the delay activated. This
indication shall be suppressed when the
VACIE enters the voice alarm condition.
7.5 Phased evacuation (option with
requirements)
Plena Voice Alarm System does not
accommodate phased evacuation.
The VACIE may have a provision to phase the
warning signals to the emergency loudspeaker
zones. The facility shall be configurable at
access level 3. There may be provision to
switch on and switch off the phased
evacuation sequence by means of a manual
operation at access level 2 (see Annex A for
information on access levels).
7.6 Silencing of the voice alarm
condition
Plena Voice Alarm System is compliant.
7.6.1 Silencing of the voice alarm condition
from the CIE
7.6.1.1 Where the voice alarm condition has
been triggered from the CIE, the VACIE shall
respond appropriately to a silence instruction
from the CIE.
Voice alarm calls triggered from the CIE
can also be stopped from the CIE. To reset
the voice alarm condition an Acknowledge
Emergency is possible for CIE and front
panels of the controller and remote control
panels.
7.6.1.2 The silencing procedure may allow for
the completion of messages in the process of
being broadcast.
If a voice alarm call is activated from the
contacts it is configurable whether or not
to stop or finish the message. If the alarm
condition is reset from the front panel or
the call is aborted from the front panel of
the controller and remote control panels,
the message is topped immediately.
7.6.2 Manual silencing of the voice alarm
condition (option with requirements)
7.6.2.1 It shall be possible to manually silence
the voice alarm message from the VACIE at
access level 2.
Plena Voice Alarm System offers the
possibility to stop voice alarm calls by de-
activating (or re-activating) the contact or
key that started the call, or. By using the
front panel key on the controller or remote
control panels, the messages can be
routed differently, or overruled.
7.6.2.2 Following silencing, it shall be possible
to re-activate the voice alarm message at
access level 2.
Voice alarm call can be re-activated by
starting that call again from a contact,
routing it to the zone(s) again.
7.7 Reset of the voice alarm condition Plena Voice Alarm System is compliant.
7.7.1 Reset of the voice alarm condition from
the CIE
Clause / Requirement Compliance Signature