126 en | Plena Voice Alarm System
9922 141 1037x (V2.16) | V0.6 | 2011.09 Installation and Operation manual Bosch Security Systems B.V.
Where the voice alarm condition has been
triggered from the CIE, the VACIE shall respond
appropriately to a reset instruction from the
CIE.
See 7.6.1.1.
7.7.2 Manual reset of the voice alarm condition
(option with requirements)
7.7.2.1 It shall be possible to reset the voice
alarm condition from the VACIE at access level
2 by means of a separate manual control. This
control shall be used only for reset and may be
the same as that used for reset from the fault
warning condition.
To reset the voice alarm condition an
Acknowledge Emergency and Reset
Emergency action is required. Plena Voice
Alarm System has dedicated acknowledge
and reset buttons on the front panel of the
controller and remote controls.
7.7.2.2 Following a reset operation, the
indication of the correct functional condition
corresponding to any received signals shall
either remain or be re-established within 20 s.
After a reset operation, the Plena Voice
Alarm System will immediately indicate the
functional condition it is currently in. It will
also immediately (<<1 s) respond to
received signals that will bring it into
another functional condition.
7.8 Output to fire alarm devices
(option with requirements)
This option is not supported by the Plena
Voice Alarm System.
In addition to the voice alarm outputs the
VACIE may have provision for the automatic
transmission of fire alarm signals to fire alarm
devices such as beacons and vibrating devices.
In this case, the following shall apply:
a it shall be possible to de-activate the fire
alarm devices at access level 2;
b following de-activation, it shall be possible
to re-activate the fire alarm devices at
access level 2;
c the fire alarm devices shall not be de-
activated automatically;
d it shall be possible to configure the VACIE
at access level 3 to automatically reactivate
the fire alarm devices if an alarm is
reported in an other zone.
7.9 Voice alarm condition output
(option with requirements)
Plena Voice Alarm System is compliant.
The VACIE may have provision for transmitting
a signal that is in the voice alarm condition. In
this case, it shall activate the output only in the
voice alarm condition.
The Plena Voice Alarm System transmits a
signal that it is in the voice alarm condition
via the Open Interface, and via the status
contact.
Clause / Requirement Compliance Signature