136 en | Plena Voice Alarm System
9922 141 1037x (V2.16) | V0.6 | 2011.09 Installation and Operation manual Bosch Security Systems B.V.
b a separate light emitting indicator and/or
alphanumeric display for each voice alarm
zone and/or an indication for group(s) of
voice alarm zones.
The voice alarm condition is indicated on
the Plena Voice Alarm System per zone by a
red indicator on the controller, routers and
remote control panels.
NOTE - These indicators may not necessarily
indicate which emergency message is being
broadcast in each voice alarm zone.
10.3 Indication of the voice alarm
zones in fault condition
Plena Voice Alarm System is compliant.
The indication for the fault condition which
would prevent the generation and transmission
of the voice alarm signal to the voice alarm
zone(s) associated with each manual control
shall be available without any manual action
and shall not be suppressed. This indication
shall be by
a a separate light emitting indicator (the
general fault indicator), and
Plena Voice Alarm System does not have a
common fault indicator. A light emitting
device must be connected to the general
fault output to achieve this.
b an indication for each voice alarm zone
and/or an indication for defined group(s)
of zones.
The Plena Voice Alarm System provides a
visible indication when it is in the fault
warning condition via the fault LED of the
corresponding zone for loudspeaker line
related faults and key (mandatory)
monitored elements. A fault indicator of an
individual zone may indicate more than one
fault. Common to those fault are that they
occur in the indicated zone (e.g.
loudspeaker line short circuit, open
connection, ground short of the same
zone).
10.4 Indication of the voice alarm
zones in disablement condition
The indication for the disablement condition in
the voice alarm zone(s) associated with each
manual control shall be available without any
manual action and shall not be suppressed.
This indication shall be by
Plena Voice Alarm System does not
support the optional disablement
condition.
a a separate light emitting indicator (the
general disablement indicator), and
b an indication for each voice alarm zone
and/or an indication for defined group(s)
of zones.