Plena Voice Alarm System | en 137
Bosch Security Systems B.V. Installation and Operation manual 9922 141 1037x (V2.16) | V0.6 | 2011.09
11 Interface to external control device(s) (option with the requirements)
Clause / Requirement Compliance Signature
The VACIE may have provision for interfacing to
external control device(s) such as standardized
user interfaces required by local regulations. In
this case, the following shall apply:
Plena Voice Alarm System does not
support the Interface to external control
device(s) option.
a the interface shall allow only access level 1
and 2 functions;
b the mandatory functions of the VACIE shall
not be overridden;
c any short-circuit, interruption or earth fault in
the transmission path to the external
device(s) shall
not prevent the mandatory function of
the VACIE, and
be indicated on the VACIE, at least by
means of the general fault warning
indicator.
NOTE - The external control devices should
comply with available local or national standards.