RE 92650/2020-03-03, Bosch Rexroth AG
23 Axial piston variable pump | A1VO Series 10
Installation instructions
1) Because complete air bleeding and filling are not possible inthis
position, the pump should beair bled and filled inahorizontal
position before installation.
Installation instructions
General
The axial piston unit must befilled with hydraulic fluid and
air bled during commissioning and operation. This must
also beobserved following alonger standstill astheaxial
piston unit may empty viathehydraulic lines.
Particularly with the "drive shaft up/down" installation
position, filling and air bleeding must be carried out
completely as there is, for example, adanger ofdry
running.
The leakage in the pump housing must be discharged tothe
reservoir via the highest available tank port (L
1
, L
2
).
For combinations ofmultiple units, the leakage fluid must
be drained off at each pump.
If ashared drain line isused for several units, make sure
that therespective case pressure ineach unit isnot
exceeded. The shared drain line must bedimensioned
toensure that themaximum permissible case pressure
ofall connected units isnot exceeded inany operating
conditions, particularly atcold start. If this isnot possible,
separate drain line must belaid, ifnecessary.
To achieve favorable noise values, decouple all connecting
lines using elastic elements and avoid above-reservoir
installation.
Inall operating conditions, the suction lines and the drain
lines must flow into the reservoir below the minimum fluid
level. The permissible suction heighth
S
results from the
total pressure loss. However, it must not behigher than
h
Smax
=
800 mm. The minimum suction pressure
atportSmust also not fall below 0.8bar abs. during
operation and during acold start.
When designing the reservoir, ensure adequate distance
between the suction line and the case drain line. This
prevents theheated return flow from being drawn directly
back into thesuction line.
Notice
Incertain installation positions, an influence
ontheadjustment orcontrol can beexpected. Gravity,
dead weight and case pressure can cause minor
characteristic shifts and changes inactuating time.
For key, see page 24.
Installation position
See thefollowing examples 1 to11.
Further installation positions are available upon request.
Recommended installation position: 1 and 2
Below-reservoir installation (standard)
Below-reservoir installation means that theaxial piston unit
isinstalled outside ofthereservoir below theminimum
fluid level.
Installation position Air bleed Filling
1
S
F
SB
h
h
L
F, L
1
L
1
2
S
L
2
SB
h
t min
h
min
F
F, L
2
L
2
3
S
L
1
SB
h
t min
h
min
F
F, L
1
or L
2
L
1
or L
2
4
1)
L
2
SB
h
t min
h
min
F, L
1
or L
2
L
1
or L
2