01.2015, USL00010, Bosch Rexroth Corp.
21 VerifyCommutationOset
21.1VerifycommutationosetwithdigitalHallorwithoutHallsensor
21.1.1 StepsforverifyingcommutationosetwithdigitalHallorwithoutHallsensor:
1. If not already, start Easy Startup Mode and enable power.
2. Select Cmd value input.
3. Select Torque input.
4. Enter a safe torque/force command value, suggest start from low to high, for following
cases:
• Value = 10-30%, for zero to light payload on carriage
• Value = 20-50%, for medium to heavy payload on carriage
5. Press the ± arrow keys to command negative/positive current control movement of the axis.
ATTENTION:
Prior to this command, the axis position must allow UNRESTRICTED MOVEMENT!
WARNING: Stay clear, axis will MOVE!
6. If axis moves smoothly in the expected direction, then the commutation oset has been
veried*. If not, then repeat Determine Commutation Oset procedure (see owchart).
NOTE: Veried* = this is a practical eld method using current loop control only, i.e. without
inuence of the velocity and position loop controllers. Depending on the application, further
commutation oset optimization may be required. For further details, please see the Rexroth
IndraDrive MPx-17 (or later) Functions Applications Manual sections “Commutation Setting”
and “Sine-Wave Method”.
35 VerifyCommutationOset