ctrlX SAFETY "SafeMotion"
Transition functions
Bosch Rexroth AG
R911404905,
Edition 02
The transition function "Safe stop 1" is selected via the active "SafeMotion"
profile using P-0-3264.
The status of the transition function "Safe stop 1" is displayed by the param-
eter P-0-3264.0.1, .
Parameters involved
The following parameters are used in conjunction with the transition function
"Safe stop 1":
P‑0‑3238, SMO: Active velocity threshold
P‑0‑3255, SMO: Velocity threshold for Safe standstill
P‑0‑3263.0.1, SMO: Configuration of stopping process
P‑0‑3280.0.1, SMO: Configuration of operation mode transitions
P‑0‑3280.0.2, SMO: Max. Transition time normal oper. to safe standstill
P‑0‑3280.0.3, SMO: Max. Transition time between safe operating states
Diagnostic messages involved
The following diagnostic messages can be generated in conjunction with the
transition function "Safe stop 1":
C0214 SMO: Incorrect configuration
F7050 Maximum transition time exceeded
F7051 Safely-monitored deceleration exceeded
F8350 Maximum transition time exceeded
F8351 Safely-monitored deceleration exceeded
With the transition function "Safe stop 1" activated, the display of the panel
does not show any specific message.
Transition function
Basic principle
When the transition function “Safe stop 1 (SS1)“ is activated, the drive is
decelerated in a safely monitored way. After the deceleration process has been
completed, the safety function “Safe torque off (STO)“ is activated and the
energy supply to the motor is safely interrupted. The motor cannot generate any
torque/any force and therefore no dangerous movements.
The transition function “Safe stop 1“ detects a successful deceleration process,
if the following conditions have been fulfilled:
The motor has stopped, i.e. the actual velocity is smaller than the value
parameterized in "P‑0‑3255, SMO: Velocity threshold for Safe standstill",
and
the drive is no longer in control.
Configuring the transition function
To use the transition function "Safe stop 1", it
has to be configured via the parameter "P‑0‑3280.0.1,
SMO: Configuration of operation mode transitions“ during the commissioning
of safety technology.
The transition function "Safe stop 1" can be executed in 8 variants, as the table
below shows:
Safety functions