Bosch Rexroth EFC 3600 Series Inverter
10. How to connect and configure a Run/Stop switch
with Forward/Reverse selection
The parameters described in Section 5 enable
Run/Stop operation via the red and green
buttons on the Inverter.
If this is unsuitable for the application, remote
switches can be used instead.
This section explains how to enable 2-wire
control with Run/Stop and Forward/Reverse
commands via separate selector switches.
Note that once this procedure is complete, the
Run/Stop buttons on the Inverter can no longer
be used.
Access to additional parameters
Default is 0 for Basic Parameters. Set at to enable Extended Parameters.2
Set to for IO Terminals on the Inverter1
Set to for 2-wire control with Run/Stop and Forward/Reverse1
Set to for run forward command on X123
Set to for run reverse command on X224
10.1 Parameters to change for remote Run/Stop
10.2 Connecting the Switch
A wiring diagram is shown in the illustration
opposite.
The SC terminal is a common connection for
terminals X1-X5 and has no other function.
Two suitable 2 position NO ( )
switches should be installed: One between
terminals SC and X1 (Run/Stop) and the other
between terminals SC and X2
(Forward/Reverse).
Note that the Forward/Reverse switch only
selects the direction of rotation - it will not start
or stop the motor.
If the application only requires the motor to turn
in one direction, the Forward/Reverse switch
can be omitted.
Normally Open
EFC 3600
I/O Terminal
Blocks
13
X1 SCX2
12
R
32 1
Switch, 2 Position
Normally Open
“Forward / Reverse”
Switch, 2 Position
Normally Open
“Run / Stop”