Easy Start Guide
Page 5
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission.
©
4. Parameters - overview
Access to additional parameters
Set at to enable Extended Parameters ( .2 Default is 0 for Basic Parameters)
Maximum frequency of the . Set to for most applications.Inverter 50.00
Maximum frequency of .speed reference (eg. keypad dial) Set to for most applications.50.00
Set to for most applications (Default is 00.00).05.00
Set to to enable Minimum Frequency.1
Acceleration ramp in seconds
Default is . Increase or decrease if required.5
Deceleration ramp in seconds
Default is . Increase or decrease if required.5
Default is . Set to 1 if the motor is driving a Fan or Pump.0
Rated motor frequency in Hz
Default is 50.00. Change to 60.00 for 60Hz motor only - otherwise set at 50.00
Set to match motor nameplate - eg. 1380
Set to match motor nameplate - eg. 0.8 (for 0.75kW)
Set to match motor nameplate - eg. 230
Set to match motor nameplate - eg. 3.34
The Inverter contains a number of settings
which can be changed to tailor it for use in a
wide range of applications. These settings are
known as parameters.
Parameters are typically referred to by code or
number (eg. s2.04 = Rated Motor Current) with
a description available in the manual.
The parameters contain critical information
essential to the correct operation of the
Inverter. Therefore, they should at least be
checked by the user before the Inverter is
operated for the first time.
The parameters listed in section 5 are intended
to provide a starting point to allow for basic
operation of the EFC 3600 Inverter.
5. Parameters to set before use
See section 6 to learn how to set a parameter value.
Set the following parameters to allow the EFC
3600 to control a motor with Run, Stop and
Speed Control from the keypad.
If any of the parameters have been changed
previously, follow the procedure in section 13
to reset the Inverter to Factory Defaults.
5.1 Parameters to check and values to set
Bosch Rexroth EFC 3600 Series Inverter