HCS01.1E-W0003...W0013-x-02, HCS01.1E-W0005-x-03, HCS01.1E-W0008-x-03
HCS01.1E-W0003...W0013-x-02, HCS01.1E-W0005-x-03, HCS01.1E-W0008-x-03
View Identifica‐
tion
Function
L1 Connection to supply mains (L1)
L2 Connection to supply mains (L2)
L3 Connection to supply mains (L3)
Terminal block Unit Min. Max.
Connection cable
Stranded wire
mm
2
0,25 2,5
AWG 24 12
Stripped length mm 8
Occurring current load and minimum required
connection cross section
See technical data of device used (I
LN
and A
LN
)
Occurring voltage load See technical data of device used (U
LN
or U
LN_nenn
)
Fig.5-4: Function, Pin Assignment, Properties
HCS01.1E-W0018-x-03, HCS01.1E-W0028-x-03
HCS01.1E-W0018-x-03, HCS01.1E-W0028-x-03
View Identifica‐
tion
Function
L1 Connection to supply mains (L1)
L2 Connection to supply mains (L2)
L3 Connection to supply mains (L3)
Terminal block Unit Min. Max.
Connection cable
Stranded wire
mm
2
0,25 6,0
AWG 24 8
Stripped length mm 10
Occurring current load and minimum required
connection cross section
See technical data of device used (I
LN
and A
LN
)
Occurring voltage load See technical data of device used (U
LN
or U
LN_nenn
)
Fig.5-5: Function, Pin Assignment, Properties
22/65 Bosch Rexroth AG | Electric Drives
and Controls
Rexroth IndraDrive | Instruction Manual
Instructions for Use