5.2.5 X5, Motor Connection
Important Notes
WARNING
Lethal electric shock by live parts with more than 50 V!
Exclusively operate the device
● with plugged on connectors (even if there haven't been any lines connec‐
ted to the connectors) and
● with connected equipment grounding conductor!
CAUTION
Risk of damage to the device!
Provide strain relief for the terminal connectors of the device in the control cab‐
inet.
Notes on Installation
The equipment grounding conductor is connected directly to the device and not
via the connection point X5 (see description for connection of equipment
grounding conductor).
The indicated connection cross sections are the cross sections which can be
connected. Dimension the required cross section of the connection lines ac‐
cording to the occurring current load.
● For optimum shield contact of the motor power cable, use the
supplied accessory HAS09.
● For the connection between drive controller and motor, use
our ready-made motor power cables, where possible (see
documentation "Rexroth Connection Cables").
● When using NFD03.1 mains filters, the maximum allowed con‐
ductor cross section is limited to 4 mm
2
.
X5, Motor Connection HCS01.1E-W0003…W0013-x-02, -W0005-x-03, -W0008-x-03
View Identifica‐
tion
Function
A1 For power connection U1 at motor
A2 For power connection V1 at motor
A3 For power connection W1 at motor
Screw connection at connector Unit Min. Max.
Connection cable
Stranded wire
mm
2
0,25 2,5
AWG 24 12
Stripped length mm 8
Occurring current load and minimum required
connection cross section
A See technical data of device used (I
out
)
Occurring voltage load V See technical data of device used (U
out
)
Instruction Manual | Rexroth IndraDrive Electric Drives
and Controls
| Bosch Rexroth AG 23/65