How to Remove the Touch Guard:
U
DC
DC bus voltage
30 Min. ! Before accessing the device, wait at least 30 minutes after switching off
the supply voltages to allow discharging.
1. With a small screwdriver (blade width < 3 mm), push the fixing device
outwards and simultaneously lever out the touch guard.
2. Pull off touch guard.
3. Store the touch guard in a place where you can find it later on. If you
want to operate the device without DC bus connector, you have to have
to plug the touch guard on connection point X77 again.
Fig.5-12: How to Remove the Touch Guard
Fig.5-13: DC Bus Connector at Device
Instruction Manual | Rexroth IndraDrive Electric Drives
and Controls
| Bosch Rexroth AG 29/65
Instructions for Use