Bronkhorst®
Instruction Manual EL-FLOW® Select 9.17.099F34
4.2 Special parameters
Init Reset is used to unlock secured parameters (marked with a B symbol) for writing. It supports the following values:
unlocked, secured parameters can be read and written to
locked, secured parameters are read-only
At power-up, Init Reset is always set to ‘Locked’ (value 82).
This parameter is used to reset the program, counter or alarms.
Reset and disable counter
Reset firmware program (soft reset)
Reset Alarm info error bit
Reset Alarm info warning bit
The Reset parameter may be disabled by Reset Alarm Enable or Reset Counter Enable. Make sure the value is accepted
by sending value 0 first.
Sending any text string value between 1 and 9 to this parameter makes the indication LEDs (if present) blink for a couple of
seconds. This can be useful in order to identify a specific device in a large fieldbus network.
*) Modbus only supports value 14592
Control Mode is used to select different control modes of the instrument and determines from which source(s) it accepts a
setpoint. The following control modes are available:
Acting as slave instrument on FLOW-BUS
RS485 only: FLOW-BUS
master output x Slave
Factor/100%
Controller disabled, valve closed
Controller disabled, valve frozen in current position