Bronkhorst®
Instruction Manual EL-FLOW® Select 9.17.099F38
0xF108…0xF10A/ 61705…61707
Device type information string; this parameter contains an abbreviation referring to the identification number.
4.5 Alarms
Alarm settings are most easily accessible using FlowPlot or FlowView or a Bronkhorst® readout and control unit.
The built-in alarm functionality can be used to handle different alarm types:
· system errors and warnings
· min/max alarms
· response alarms
· batch alarms
· master/slave alarms
The used alarm type can be set with parameter Alarm Mode. When an alarm is activated, the type can be read out using
parameter Alarm Info. An automatic setpoint change can be set using the parameters Alarm Setpoint Mode and Alarm New
Setpoint. It is also possible to set an alarm delay, to prevent overreaction to small disturbances, using parameter Alarm Delay
Time. The methods by which an alarm can be reset are controlled by Reset Alarm Enable.
Alarm on limits related to setpoint (response alarm)
Alarm at power-up(e.g. after power-down)
(For DeviceNet™ instruments, only modes 0 and 1 are available)
This parameter provides information about the event type(s) that triggered an alarm situation. The value is a bit-wise
summation of the issued alarm types; convert the value to binary to see which types are issued. The following alarm types
can be issued:
Measure < Alarm minimum limit
Measure > Alarm maximum limit
Batch counter reached its limit
· This bit only: Power-up alarm
Alarm possibly caused by a power dip
· If combined with bit 2 or 3:
Response alarm
Difference between Measure and Setpoint too big
Setpoint out of limits (caused by Slave factor)