EasyManuals Logo

Bryant LEGACY 580J User Manual

Bryant LEGACY 580J
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
11
Table 6 MINIMUM -- MAXIMUM AIRFLOW RATINGS -- NATURAL GAS & PROPANE
UNIT HEAT LEVEL
COOLING HEATING
MINIMUM MAXIMUM MINIMUM MAXIMUM
580J**04
LOW
900 1500
990 2190
MED 1000 1550
HIGH --- ---
580J**05
LOW
1200 2000
990 2190
MED 1330 2460
HIGH 1390 2220
580J**06
LOW
1500 2500
990 2730
MED 1330 2880
HIGH 1390 2780
580J**07
LOW
1800 3000
990 3640
MED 1330 3450
HIGH 1390 3170
580J**08
LOW
2250 3750
1900 4750
MED 2100 3900
HIGH 2270 3780
580J**09
LOW
2550 4250
1900 4750
MED 2100 4560
HIGH 2270 4250
580J**12
LOW
3000 5000
2100 5470
MED 2620 5670
HIGH 2650 5290
580J**14
LOW
3600 6000
2100 6830
MED 2620 6800
HIGH 2650 7410
580J**16
LOW
4500 7500
2450 7500
MED 3000 6750
HIGH 3990 7200
580J

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bryant LEGACY 580J and is the answer not in the manual?

Bryant LEGACY 580J Specifications

General IconGeneral
BrandBryant
ModelLEGACY 580J
CategoryAir Conditioner
LanguageEnglish

Related product manuals