Table 6 MINIMUM -- MAXIMUM AIRFLOW RATINGS -- NATURAL GAS & PROPANE
UNIT HEAT LEVEL
COOLING HEATING
MINIMUM MAXIMUM MINIMUM MAXIMUM
580J**04
LOW
900 1500
990 2190
MED 1000 1550
HIGH --- ---
580J**05
LOW
1200 2000
990 2190
MED 1330 2460
HIGH 1390 2220
580J**06
LOW
1500 2500
990 2730
MED 1330 2880
HIGH 1390 2780
580J**07
LOW
1800 3000
990 3640
MED 1330 3450
HIGH 1390 3170
580J**08
LOW
2250 3750
1900 4750
MED 2100 3900
HIGH 2270 3780
580J**09
LOW
2550 4250
1900 4750
MED 2100 4560
HIGH 2270 4250
580J**12
LOW
3000 5000
2100 5470
MED 2620 5670
HIGH 2650 5290
580J**14
LOW
3600 6000
2100 6830
MED 2620 6800
HIGH 2650 7410
580J**16
LOW
4500 7500
2450 7500
MED 3000 6750
HIGH 3990 7200