69
5. After a call for heating, the main burners should light
within 5 seconds. If the burner does not light, then there is
a 22 second delay before another 5 second try. If the
burner still does not light, the time delay is repeated. If the
burner does not light within 15 minutes, there is a lockout.
To reset the control, break the 24 v power to W1.
6. The evaporator-fan motor will turn on 45 seconds after
burner ignition.
7. The evaporator-fan motor will turn off in 45 seconds after
the thermostat temperature is satisfied.
8. Adjust airflow to obtain a temperature rise within the
range specified on the unit nameplate.
NOTE: The default value for the evaporator-fan motor on/off de-
lay is 45 seconds. The Integrated Gas Unit Controller (IGC) modi-
fies this value when abnormal limit switch cycles occur. Based
upon unit operating conditions, the on delay can be reduced to
0 seconds and the off delay can be extended to 180 seconds. When
one flash of the LED is observed, the evaporator-fan on/off delay
has been modified.
If the limit switch trips at the start of the heating cycle during the
evaporator on delay, the time period of the on delay for the next
cycle will be 5 seconds less than the time at which the switch
tripped. (Example: If the limit switch trips at 30 seconds, the evap-
orator-fan on delay for the next cycle will occur at 25 seconds.) To
prevent short-cycling, a 5 second reduction will only occur if a
minimum of 10 minutes has elapsed since the last call for heating.
The evaporator-fan off delay can also be modified. Once the call
for heating has ended, there is a 10 minute period during which
the modification can occur. If the limit switch trips during this
period, the evaporator-fan off delay will increase by 15 seconds.
A maximum of 9 trips can occur, extending the evaporator-fan
off delay to 180 seconds.
To restore the original default value, reset the power to the unit.
To shut off unit, set system selector switch at OFF position. Re-
setting heating selector lever below room temperature will tem-
porarily shut unit off until space temperature falls below thermo-
stat setting.
VENTILATION (CONTINUOUS FAN)
Set fan and system selector switches at ON and OFF positions, re-
spectively. Evaporator fan operates continuously to provide con-
stant air circulation. When the evaporator-fan selector switch is
turned to the OFF position, there is a 30 second delay before the
fan turns off.
FASTENER TORQUE VALUES
Table 39 — Torque Values
FASTENER LOCATIONS TORQUE VALUES
Supply fan motor mounting
120 in.-lbs (13.6 Nm) ± 12 in.-lb
(1.4Nm)
Supply fan motor adjustment
plate
120 in.-lbs (13.6 Nm) ± 12 in.-lb
(1.4Nm)
Motor pulley setscrew
72 in.-lbs (8.1 Nm) ± 5 in.-lb
(0.6 Nm)
Fan pulley setscrew
72 in.-lbs (8.1 Nm) ± 5 in.-lb
(0.6 Nm)
Blower wheel hub setscrew
72 in.-lbs (8.1 Nm) ± 5 in.-lb
(0.6 Nm)
Bearing locking collar setscrew
50 in.-lbs (6.2 Nm) – 60 in.-lb
(6.8 Nm)
Compressor mounting bolts
65 in.-lbs (7.3 Nm) – 75 in.-lb
(8.5Nm)
Condenser fan motor mounting
bolts
20 in.-lbs (2.3 Nm) ± 2 in.-lb
(0.2 Nm)
Condenser fan hub setscrew
84 in.-lbs (9.5 Nm) ± 12 in.-lb
(1.4 Nm)