EasyManuals Logo

Buderus Logamatic 2107 Installation And Service Instructions

Buderus Logamatic 2107
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
7.7 Maximum boiler temperature
The maximum boiler temperature is the highest target temperature the boiler will
reach. The burner should switch off no later than when this temperature is
reached (this applies to heating mode and DHW mode).
The factory default is 176°F (80°C).
Changing the maximum OFF temperature
+
Press the "Display" key and "Install" key at the same time to call up the service
level. "AMERICAN" appears as the first main menu.
Turn the dial until "BLR TEMP" is shown.
Press "Display" to call up a submenu.
"FREEZE TEMP" appears.
Turn the dial until "MAXTEMP 1" is shown.
+
Hold down "Display" and turn the dial until the
required value appears (in this case 167°F
(75°C)).
Release "Display" to store your input.
Press "ENTER" to return to the next higher level.
176
MAXTEMP 1
°F
167
MAXTEMP 1
°F
USER NOTE
Ensure that the boiler water aquastat dial is set above the maximum boiler
temperature, as it will overwrite the maximum boiler temperature.
Input range Factory setting
Maximum OFF temperature
158°F – 210°F
(70°C – 99°C)
176°F (80°C)
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 27
7
General data

Table of Contents

Other manuals for Buderus Logamatic 2107

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Buderus Logamatic 2107 and is the answer not in the manual?

Buderus Logamatic 2107 Specifications

General IconGeneral
CategoryControl Systems
TypeHeating Control Unit
Voltage230 V
Frequency50 Hz
Protection classIP20
Ambient temperature0°C
ApplicationHeating systems

Related product manuals