11 DHW recirculation pump
The DHW recirculation pump ensures a constant supply of hot water to the taps.
It is automatically activated with DHW heating and the pump runs in intermittent
or continuous mode if at least one heating circuit is in normal heating mode (day
mode), or if DHW heating is in day mode.
The DHW recirculation pump runs continuously in the "ON" position.
The factory default is "2", i.e. 2 pump runs per hour, running for 3 minutes each
time (Fig. 10).
The intermittent mode may be set to 1 to 6 pump starts per hour in order to
minimize the operating costs of the recirculation pump. This setting saves
energy while ensuring comfort.
Fig. 10 Illustration of the DHW recirculation pump running time with factory setting 2
3
3 minutes
ON
OFF
1 hour
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 47
11
DHW recirculation pump

Table of Contents

Other manuals for Buderus Logamatic 2107

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Buderus Logamatic 2107 and is the answer not in the manual?

Buderus Logamatic 2107 Specifications

General IconGeneral
CategoryControl Systems
TypeHeating Control Unit
Voltage230 V
Frequency50 Hz
Protection classIP20
Ambient temperature0°C
ApplicationHeating systems

Related product manuals