Changing the recirculation pump run time
+
Press the "Display" key and "Install" key at the same time to call up the service
level. "AMERICAN" appears as the first main menu.
Turn the dial until the "RECIRCPUMP 2" main menu is displayed.
+
Hold down the "Display" key and turn the dial anti-clockwise until the required
value appears (in this case "4").
Release "Display" to store your input.
Press "ENTER" to return to the next higher level.
2
RECIRCPUMP
4
RECIRCPUMP
Input range Factory setting
DHW recirculation pump
OFF
1
2
3
4
5
6
ON
2