EasyManuals Logo

Buderus Logamatic 2107 Installation And Service Instructions

Buderus Logamatic 2107
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
Changing the differential temperature
+
Press the "Display" key and "Install" key at the same time to call up the service
level. "AMERICAN" appears as the first main menu.
Turn the dial until "CIRCUIT 01" or "CIRCUIT 02" is displayed.
Press "Display" to call up a submenu.
"PERIM HTG" or "FLOOR HTG" appears.
Turn the dial until "ROOM COMP" is shown.
+
Hold down the "Display" key and turn the dial until the desired value appears (in
this case "OFF").
Release "Display" to store your input.
Press "ENTER" to return to the next higher level.
6
ROOM COMP
°F
OFF
ROOM COMP
Input range Factory setting
Differential temperature
OFF
2 – 18°F (1°C – 10°C)
6°F (3°C)
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 39
8
Heating circuit data

Table of Contents

Other manuals for Buderus Logamatic 2107

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Buderus Logamatic 2107 and is the answer not in the manual?

Buderus Logamatic 2107 Specifications

General IconGeneral
CategoryControl Systems
TypeHeating Control Unit
Voltage230 V
Frequency50 Hz
Protection classIP20
Ambient temperature0°C
ApplicationHeating systems

Related product manuals