12
Technical data
7 TECHNICAL DATA
7.1 Conformity
TheType2301globecontrolvalveconformstotheEUdirectives
aspertheEUDeclarationofConformity(ifapplicable).
7.2 Standards
Theappliedstandards,whichareusedtodemonstrateconformity
withEUDirectives,arelistedintheEU-typeexaminationcerticate
and/ortheEUDeclarationofConformity(ifapplicable).
AccordingtoPressureEquipmentDirectiveobservethefollowing
operating conditions:
Housing size
DN
Maximum pressure for compressible uids
of Group1 (dangerous gases and vapours
according to Art. 3, No.1.3, letter a, rst
dash)
DN65 15bar
DN80 12.5bar
DN100 10bar
7.3 Type label
00297969
2301 B PTFE Kvs4,3 lin
PS 16bar Tmed -10...+130°C
Flow 1 2
W17AL
see manual for derating
CEmarking
Permittedmedium
temperature
Controlcharacter-
isticform(linear)
Type
Controlfunction
(CF)
Sealmaterial
1)
Identication
numberofthe
device
Flow direction
Permittedmedium
pressure
Manufacturerdate
(encrypted)
Forderating,pleasereferto
theoperatinginstructions.
Flow capacity in serial
conditions
1) Foravariantdescriptionsee“1.1Denitionofterms/abbreviations”
Type2301