28
Installation
8.4.1 Connecting the control medium
Connectthecontrolmediumtothepilotairport(1)(3–7bar;
instrumentair,oil-/water-/dust-free).
Mounttheexhaustairlineorasilencerontotheexhaustairport
(3)and,ifavailable,ontotheadditionalexhaustairport(3.1).
Forusageinanaggressiveenvironment,werec-
ommendusingapneumatichosetodrainallfreepneu-
maticportsinaneutralatmosphere.
Pilot air port
Exhaustairport
Additionalexhaustairport
onlywithservo-assisted
actuatingsystemforhighair
owrate
(actuatorsizeø130)
1
3
3.1
Fig.16: Pneumaticconnection
Pilot air hose:
Pilotairhosesofsizes6/4mmor¼"canbeused.
OptionallyapilotairportviaG⅛"threadispossible.
8.5 Start-up
PerformtheX.TUNEafterinstallingthedevice.Thisfunction
presetsthecontrolparameters.
Seecontrolunitoperatinginstructionsforadescription.
8.6 Disassembly
DANGER!
Risk of injury from discharge of pressure and escaping
medium.
Dismantlingadevicewhichisunderpressureishazardousdue
toasuddendischargeofpressureorescapingmedium.
Beforedisassembly,shutothepressureandventalllines.
Procedure:
Loosenpneumaticconnection.
Disassemblethedevice.
Type2301