TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
Fan output (Fan) - adjust using gas
analyzer.
Mode : Mediumoutputmode
– It is indicated by two ames.
We recommend to set value at 50% of
the main mode.
Pelletaugerrunningme(Feed)3sec.
(12,5kW;6х50%=3)
Maincombusoncycle(Cycle)20sec.
(recommended)
Fan output (Fan) - adjust using gas
analyzer.
Mode : Low output mode – It is
indicated by one ame.
We recommend to set value at 35%
(0,35) of the main mode.
Pellet auger running me (Feed)1,1
sec.(7,5kW;6х35%=1,1)
Maincombusoncycle(Cycle)20sec.
(recommended)
Fan output (Fan) – adjust using gas
analyzer.
i
Important: You use a burner
whose carbon footprint values
are approximately (СО = 100
ppm), which is 2.5 times lower
than the maximum allowed
limits for harmful emissions in
the EU Member States. Thus
you can reduce the amount of
harmfulemissionandcontribute
toenvironmentprotection.
Important: For each of the
output modes the optimal fan
setting is tweaked by using gas
analyzer to control the oxygen
amountregisteredbythedevice
(withintherange8%÷10%,and
forthelowermodesupto13%).
The specific setting depends
alsoontheinternalresistanceof
the boiler combustionchamber
on which the burner has been
installed as well as on the
chimneydraught.Thereforeitis
notpossibletoprovideherethe
exact value for the fan output
and it must be entered by a
competent installer or service
technicianusinggasanalyzer
11. WARRANTY TERMS
The warranty terms are described in the
Service booklet included in the supply.