Fan output (Fan) - adjust using gas
analyzer.
Mode : Mediumoutputmode
– It is indicated by two ames.
We recommend to set value at 50% of
the main mode.
Pelletaugerrunningme(Feed) – 3sec.
(12,5kW;6х50%=3)
Maincombusoncycle(Cycle) – 20sec.
(recommended)
Fan output (Fan) - adjust using gas
analyzer.
Mode : Low output mode – It is
indicated by one ame.
We recommend to set value at 35%
(0,35) of the main mode.
Pellet auger running me (Feed) – 1,1
sec.(7,5kW;6х35%=1,1)
Maincombusoncycle(Cycle) – 20sec.
(recommended)
Fan output (Fan) – adjust using gas
analyzer.
i
Important: You use a burner
whose carbon footprint values
are approximately (СО = 100
ppm), which is 2.5 times lower
than the maximum allowed
limits for harmful emissions in
the EU Member States. Thus
you can reduce the amount of
harmfulemissionandcontribute
toenvironmentprotection.
Important: For each of the
output modes the optimal fan
setting is tweaked by using gas
analyzer to control the oxygen
amountregisteredbythedevice
(withintherange8%÷10%,and
forthelowermodesupto13%).
The specific setting depends
alsoontheinternalresistanceof
the boiler combustionchamber
on which the burner has been
installed as well as on the
chimneydraught.Thereforeitis
notpossibletoprovideherethe
exact value for the fan output
and it must be entered by a
competent installer or service
technicianusinggasanalyzer