EasyManua.ls Logo

BWT Bewazon VULW 45 - Page 25

BWT Bewazon VULW 45
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EN
25
Example: Variable mixing
Preset: The customer preset corresponds to the conventional mixing
operation,regardlessoftheozoneoutput,i.e.airowo󰀨=>mixingo󰀨=>
outputsignal=4mAairowon=>mixingon=>outputsignal=20mA
The air input for ozone mixing should be set on the injector according
to the current ozone output. That means that the ozone mixing should
beoperatedas variablemixing(see below).Todo so,theinjector's
pressure booster pump is run via a frequency converter, which in turn is
actuated by the analogue output signal. This means that less air is input,
for example, when operating at the medium ozone level, and the current
consumptionofthemixeralsodecreases,oftenquitesignicantly.
For this mode of operation, the external injector must be suitable for
operationwithavariableairow.Thesuitabilityforthismodeofope-
ration must be checked ahead of time if necessary.
Setting variable mixing
Theanalogueoutputsignalisconguredatthefactorysothatexternal
mixingcanbeoperatedconventionallyatrst.
That means:
-Ozonedeviceo󰀨=>signal=4mA=>boosterpumpo󰀨.
- Ozone device on, with level 0 to 16 => signal = 20 mA => booster
pump on with 100% pump capacity.
Whenoperatingatlevel0(signal=20mA),themixingmustrstbe
set on the corresponding valves on the injector so that it draws 100%
ofthenominalairowoftheozonedevice.
Once the valves are set this way, they must not be changed afterwards.
Next, you must determine – likewise during operation at level 0 – how
much the air ow can be reduced via the analogue signal without
causingthe airow tobecome unstableor tobe interrupted.To do
so, you must gradually decrease the value of the signal for “Operation
level0”untilallofthesignalvaluesfortheentirecontrollableairow
range are determined.
Stableoperationshouldbepossiblewithnominalairowreducedto
50 to 60%.
If, for example, stable operation is achieved at 50% of the nominal air
owwithasignalof14.0mA,thisairowcanbesetuptolevel8(which
corresponds to 50% of the ozone production capacity).
Operati-
on/level
Set
output signal (mA)
1)
Resulting
airow,approx.(%)
OFF 4.0 0.0
0 14.0 50.0
1 50.0
2 14.0 50.0
3 50.0
4 14.0 50.0
5 50.0
6 14.0 50.0
7 50.0
8 14.0 50.0
9 56.3
10 15.5 62.5
11 68.8
12 17.0 75.0
13 81.3
14 18.5 87.5
15 93.8
16 20.0 100.0
Theunit isoperated upto level8 with50% of thenominal airow.
Athigherlevels,theairowincreasesgraduallyandcontinuallywith
the ozone output.
Settings must be made according to the adjacent table.
The adjustable range between 50% and 100% is evenly distributed
overthecorrespondingrangeoflevels,i.e.abovelevel8,theairow
should increase by approx. 6.25% per level (50% of the control range
divided into 8 levels = 6.25% per step)
1) The output signal for odd levels is determined by the PLC as the
mean value of the setting for the level above and below it.

Related product manuals