Function List
BURN
Sensor burn-out/break protection
Caution: Settings affect fail safe state.
SP1 SP2
[uP.SC]
Upscale Upscale
dn.SC
Downscale Downscale
1u.2d
Upscale Downscale
1d.2u
Downscale Upscale
REU.D
Select output modes: Direct/Reverse
Caution: Settings affect fail safe state.
SP1 SP2
[1r.2d]
Reverse Direct
1d.2d
Direct Direct
1r.2r
Reverse Reverse
1d.2r
Direct Reverse
Select Reverse on SP1 for heating and Direct for
cooling applications.
19
LEVEL 3
OUTPUT CONFIGURATION
Note: ‘Read only’ after initial configuration.
rSET ALL
full
reset to factory settings required to change
SP1.D subsequently.
SP1.D
[nonE] rLY SSd rLY1 rLY2 SSd1
Select SP1 output device
SP2.D
[nonE] SSd rLY rLY2 rLY1 SSd2
Read SP2 output device
(read only)
Dual Relay and Dual SSd output options Models
3311 and 3322 are factory set. See page 22
Note: (when in initial configuration only)
Hold ✱ and ▲ or ▼ for 10 seconds to move to or
from output devices in shaded portion.