38
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© Calix. All Rights Reserved.
To wire external alarms
1. Get up to eight 24 AWG wire pairs of sufficient length to reach the far-end contacts
from the E7-2.
2. At the E7-2 end, strip approximately one inch (2.54 cm) of insulation from the alarm
wire ends.
3. Wire the E7-2 alarm inputs as follows:
a. Connect a pair of alarm wires to the first input position (AL1):
Wrap the first wire (typically black) to the AL1+ pin.
Wrap the second wire (typically white) to the AL1- pin.
b. Repeat Step 3a for each additional alarm input to use (AL2AL7), as required.
4. Wire the E7-2 alarm output position (OUT) as follows:
Wrap the first wire (typically black) to the OUT+ pin.
Wrap the second wire (typically white) to the OUT- pin.
5. Route and dress the alarm wires out to the appropriate far-end interfaces and connect per
local practice.
Refer to the Calix E7 User Guide for supported environmental alarms and alarm provisioning
information.