16 ANTIFREEZE CONTROL
16.1.1 INPUTS USED
Temperature probe at Outlet
16.1.2 PARAMETERS USED
enable probe at outlet
antifreeze heater set point
antifreeze heater differential
antifreeze alarm set-point
antifreeze alarm differential
16.1.3 OUTPUTS USED
antifreeze heater
Every pCO unit is able to manage antifreeze control providing the temperature probe at outlet is connected and enabled.
Antifreeze control is always enabled, even if the machine is OFF, both in summer and winter operating modes.
Note: the antifreeze alarm on any pCO unit shuts down the entire machine.
antifreeze set
antifreeze diff.
set. resistenza
heate
r
diff.
Antifreeze alarm
enabling
Antifreeze heater
enabling