Modular Standard HP Chiller for Carel driver
Carel code +030221236- Rel. 1.0 dated 7 July 2003
45
18.3 ENTIRE VARIABLES
Flow Type Index Description
OUT I 1 STEFA supervisor
OUT I 2 STEFA supervisor
OUT I 3 STEFA supervisor
OUT I 4 STEFA supervisor
OUT I 5 STEFA supervisor
OUT I 6 STEFA supervisor
OUT I 7 STEFA supervisor
OUT I 8 STEFA supervisor
OUT I 9 STEFA supervisor
OUT I 10 Compressors remote control
OUT
I 11 Recovery modes:
1 = recovery only
2 = chiller
3 = chiller + recovery
4 = defrosting
5 = recovery only
6 = heat pump
OUT I 12 Machine status :
0= Unit enabled
1 = shut down by alarm
2 = shut down by supervisor
3 = shut down by hour bands
4 = shut down by digital input (DIN3)
5 = shut down by local element (terminal keyboard)
6 = manual operating mode
IN/OUT I 13 Fan control by :
0 = nothing
1 = pressure
2 = temperature
OUT I 20 Count of main pump duty hours (high number word)
OUT I 21 Count of main pump duty hours (low number word)
OUT I 22 Count of compressor 1 duty hours (high word)
OUT I 23 Count of compressor 1 duty hours (low number word)
OUT I 24 Count of compressor 2 duty hours (high number word)
OUT I 25 Count of compressor 2 duty hours (low number word)
OUT I 26 Count of compressor 3 duty hours (high number word)
OUT I 27 Count of compressor 3 duty hours (low number word)
OUT I 28 Count of compressor 4 duty hours (high number word)
OUT I 29 Count of compressor 4 duty hours (low number word)
OUT I 30 Configuration of output devices for all units :
0 = CCCC
1 = CPCP
2 = CPPP
[C = compressor ; P = capacity control]
IN/OUT I 31 Selection of machine type : 0 - 23 (see manual)
OUT I 32 Type of circuit (physical) =
0 = water / air
1 = air / air
2 = water / water
IN/OUT I 33 Total number of compressor on machine
IN/OUT I 34 Number of compressors per unit (equal for all units)
IN/OUT I 35 Number of capacity controls per unit (equal for all units)
IN/OUT I 36 Number of condensation fans (1-3 for single condenser, 1-2 for double
condenser)
OUT I 37 Circuit 1 inverter speed
OUT I 38 Circuit 2 inverter speed