Motor Controllers AC Variable Frequency Drives Type VariFlex
3
RVLF
142 Specications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 13/12/2017
1. Communication Data Frame
RVLF series inverter can be controlled by a PC or other controller with the communication
protocol, Modbus ASCII Mode & Mode RTU, RS485 or RS232. Frame length maximum 80
bytes.
The network is terminated at each end with an external terminating resistor (120Ω, 1/4W)
Controller
(PLC/HMI or PC)
Slave RVLF
Station 01
Option Card
A B
Slave RVLF
Station 02
Option Card
A B
Slave RVLF
Station 03
Option Card
A B
Slave RVLF
Station FE
Option Card
A B
RS485
Interface
Response
Request
120Ω
1/4W
120Ω
1/4W
1.2. Data Format ASCII MODE
STX(3AH) Start bit = 3AH
Address Hi
Communication address (station):
2-digit ASCII code
Address Lo
Function Hi
Function code (command):
2-digit ASCII code
Function Lo
Command start address
Command start byte:
4-digit ASCII code
Command start address
Command start address
Command start address
Data length
The length of the command:
4-digit ASCII code
Data length
Data length
Data length
LRC check Hi
LRC check code:
2-digit ASCII code
LRC check Lo
END Hi
End byte :
END Hi = CR (0DH), END Lo= LF (0AH)
END Lo
Appendix 3: RVLF MODBUS
protocol

Table of Contents

Other manuals for CARLO GAVAZZI VariFlex3 RVLF Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CARLO GAVAZZI VariFlex3 RVLF Series and is the answer not in the manual?

CARLO GAVAZZI VariFlex3 RVLF Series Specifications

General IconGeneral
BrandCARLO GAVAZZI
ModelVariFlex3 RVLF Series
CategoryController
LanguageEnglish