Motor Controllers AC Variable Frequency Drives Type VariFlex
3
RVLF
Frequency upper limit
Frequency Lower limit
0
Hz
T
00-14 Acceleration time 1
Range [0.1~3600.0] s
00-15 Deceleration time 1
Range [0.1~3600.0] s
00-16 Acceleration time 2
Range [0.1~3600.0] s
00-17 Deceleration time 2
Range [0.1~3600.0] s
Preset acceleration and deceleration times by above parameters are the time taken for the
output frequency to ramp up or ramp down between the upper and the lower frequency limits.
Actual acceleration and deceleration time is calculated as follows:
(00-15)x(set frequency-the minimum starting frequency)
Actual acceleration time
V/F Mode
SLV Mode
=
(00-14)x(set frequency-the minimum starting frequency)
Maximum output frequency
Actual deceleration time=
Maximum output frequency
(00-14)x(set frequency-the minimum starting frequency
Actual acceleration time=
Motor rated frequency
(00-15)x(set frequency-the minimum starting frequency
Actual deceleration time=
Motor rated frequency
62 Specications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 13/12/2017