Motor Controllers AC Variable Frequency Drives Type VariFlex
3
RVLF
00-08 Communication Frequency Command
Range [0.00~650.00] Hz
This parameter can be used to read the set frequency in communication mode.
This parameter is only effective in the communication mode.
00-09 Frequency Command save on power down (Communication mode)
Range
[0]: disable
[1]: enable
00-09= [0] keypad frequency is saved.
00-09= [1] frequency set by communication is saved.
00-10 Initial Frequency Selection (Keypad Mode)
Range
[0]: by current freq command
[1]: by zero freq command
[2]: by 00-11
00-11 Initial Frequency Setpoint
Range [0.00~650.00] Hz
When 00-10= [0], the initial frequency will be current frequency.
When 00-10= [1], the initial frequency will be 0.
When 00-10= [2], the initial frequency will be as set by parameter 00-11.
00-12 Frequency Upper limit
Range [0.01~650.00]: Hz
00-13 Frequency Lower limit
Range [0.00~649.99] Hz
When 00-13 and the command frequency are both set to 0.00, if RUN is pressed ” Stop” is
displayed.
When frequency command is > than preset in 00-13 inverter output will ramp up from 0.00 to
the command frequency.
When 00-13> 0, and the frequency command value ≤ 00-13, inverter output will ramp up from
preset in lower limit to the command frequency.