102
LEGEND
LRA โ€“ Locked Rotor Amps
MCC โ€“ Maximum Continuous Current
RLA โ€“ Rated Load Amps
* The last two digits of the compressor model number may vary. See page 3.
NOTES:
1. RLA (rated load amps) value shown for new high efficiency models is MCC รท 1.56 - RLA.
Use this recommended (and minimum) RLA value to determine nameplate stamping, mini-
mum contactor sizing and wire sizing.
2. Compressor operating amps at any specific conditions can only be determined from a performance curve.
3. RLA values for 06D compressor protected by a calibrated circuit breaker will depend on must-trip value of circuit breaker.
4. Ohm values shown for resistance are approximate and shown for reference only. Motors from different vendors and motors of different efficiencies
can differ up to 15% from data shown.
NEW HIGH EFFICIENCY MODELS OLD STANDARD EFFICIENCY MODELS
Compressor
Model*
Electrical Data
HP
Compressor
Model*
Electrical Data
Volt MCC RLA LRA
Motor
Winding
Resistance
(Ohms)
MAX
(kW)
Volt MCC RLA LRA
06DR7420DA3150
DA3250
DA3650
575
208/230
460
17.6
44
22
11.3
28.2
14.1
64
160
80
2.6
0.42
1.7
9.8 6.5
06DR7240DA0100
DA1200
DA0600
575
208/230
460
17.6
48.8
22
12.6
34.9
15.7
50
137
62
06DR7250DA3150
DA3250
DA3650
575
208/230
46
0
17.6
44
22
11.3
28.2
14.1
64
160
80
2.6
0.42
1.7
9.8 6.5
06DR7240DA0100
DA1200
DA0600
575
208/230
460
17.6
48.8
22
12.6
34.9
15.7
50
137
62
06DR2280DA3150
DA3250
DA3650
575
208/230
460
22.2
55.5
27.8
14.2
35.6
17.8
79
198
99
2.0
0.31
1.3
12.8 7.5
06DR2280DA0100
DA1200
DA0600
575
208/230
460
22.2
55.5
27.8
15.
9
43.9
19.9
62
170
77
06DR3370DA3150
DA3250
DA3650
575
208/230
460
25
62
31
16.0
39.7
19.9
91
228
114
1.7
0.26
1.0
16.5 10
06DR3370DA0100
DA1200
DA0600
575
208/230
460
25
69
31
17.9
49.3
22.1
69
191
86
06DR5410DA0150
DA1250
DA0650
575
208/230
460
32
89
40
20.5
57.1
25.6
61
266
120
1.2
0.18
0.72
20.7 15 Not Applicable
ALLOWABLE OPERATING RANGES
NOMINAL
VOLTAGE
MAXIMUM MINIMUM
208/230
460
575
400 (50 Hz)
200 (50 Hz)
254
529
661
460
230
187
414
518
342
180

Table of Contents

Other manuals for Carlyle 06D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carlyle 06D and is the answer not in the manual?

Carlyle 06D Specifications

General IconGeneral
BrandCarlyle
Model06D
CategoryAir Compressor
LanguageEnglish

Related product manuals