102 
 
9.3.2 Inspect the Control Panel  
Maintenance consists of general cleaning and tightening of connections. Vacuum the control cabinets to eliminate 
dust build-up. If the chiller control malfunctions, refer to the Troubleshooting Guide section for control checks and 
adjustments. 
9.3.3 Inspect Purge 
A purge protects the machine against non-condensable gases. 
Make sure below procedures are done when chiller is OFF. 
1.  First drain the liquid in purge tank using refrigerant pump. In Quick Test menu, open purge drain valve, purge 
condenser valve, cooler valve and condenser drain valve. Then run refrigerant pump to drain the refrigerant 
liquid. It’ll take about 15mins. 
2.  Close all the valves connect purge and chiller. Enter Quick Test menu, check if all the solenoid valves can 
work and if vacuum pump can run. 
9.3.4 Purge Unit Maintenance 
1.  Annually inspect the condenser coil and clean if necessary. Begin to clean the coil from the fan side with use 
of high-pressure air or condenser coil cleaner. 
2. Inspect all the parts in purge system to see whether there is corrosion, terminal loosen or overheating.  
3. Yearlychange the drain filter assembly on the liquid returning line of the purge unit. 
9.3.5 Changing Refrigerant Lubrication Filters 
Change the refrigerant lubrication  filter,  motor cooling filter,  and  bearing filter  on  an annual basis or  when  the 
chiller is opened for repairs. The filters can be isolated so they can be changed with refrigerant remaining in the 
chiller.  
Strainers  such  as  2x  refrigerant pump  suction  strainers,  and  inductor  are  to  be  replaced  every 5  years  or as 
required when the  machine is open for service. These filters do not contain desiccant for moisture removal so 
changing the filter will not change the moisture indicator status. 
Change strainers/filters by closing isolation valves and slowly opening the flare fitting with a wrench and back-up 
wrench to relieve pressure. 
Moisture Removal Filter: 
The filter located on the refrigerant lubrication line to bearing and motor cooling should be replaced once a year or 
more often if filter condition indicates a need for more frequent replacement. A moisture indicator sight glass is 
located downstream of this filter to indicate the moisture level in refrigerant. If the moisture indicator turns yellow, 
locate the water source immediately by performing a thorough leak check and replace the filter. 
9.3.6 Purge Carbon Filter 
Replace only when the filter is damaged or broken. 
9.3.7 Changing refrigerant pump 
 
If changing the refrigerant pump is necessary, please follow below procedures: 
1.  Disconnect the power supply; 
2.  Open the terminal box of the refrigerant pump (Item 1, Fig. 57), and disconnect the power cable of the 
refrigerant pump;  
3.  Unbolt the refrigerant pump mounting (Item 2, Fig. 57); 
4.  Unscrew the refrigerant pump inlet and outlet joints (Item 3, Fig. 57);  
5.  Install the new refrigerant pump; 
6.  Replace the O-rings in the joints assembly, and connect the inlet and outlet of the refrigerant pump with 
new joints; 
7.  Connect the refrigerant pump power cable to the terminal box.