74 
 
• Water hardness: >0.5 mmol/l. Values between 1 and 2.5 mmol/l can be recommended. This will facilitate scale 
deposit  that  can  limit  corrosion  of  copper.  Values  that  are  too  high  can  cause  piping  blockage  over  time.  A 
carbonate hardness (TAC) below 100 is desirable. 
• Dissolved oxygen: Any sudden change in water oxygenation conditions must be avoided. It is as detrimental to 
deoxygenate the water by mixing it with inert gas as it is to over-oxygenate it by mixing it with pure oxygen. The 
disturbance of the oxygenation conditions encourages destabilisation of copper hydroxides and enlargement of 
particles. 
• Specific resistance - electric conductivity: The higher the specific resistance, the slower the corrosion tendency. 
Values above 30 Ohm·m are desirable. A neutral environment favours maximum specific resistance values. For 
electric conductivity values in the order of 20-60 mS/m can be recommended. 
• pH: Ideal case pH neutral at 20-25 °C 7 < pH < 8  
 
If the water circuit must be emptied for longer than one month, the complete circuit must be placed under nitrogen 
charge to avoid any risk of corrosion by differential aeration. Charging and removing heat exchange fluids should 
be  done  with  devices  that  must  be  included  on  the  water  circuit  by  the  installer.  Never  use  the  unit  heat 
exchangers to add heat exchange fluid. 
Piping systems must be properly vented, with no stress on waterbox pipes and covers. Use flexible connections to 
reduce the transmission of vibrations. Water flows through the cooler and condenser must meet job requirements. 
Measure the pressure drop across cooler and across condenser and compare this with the nominal values (see 
selection document). 
 
CAUTION: Water  must be  within  design limits,  clean,  and  treated  to  ensure proper  chiller  performance  and to 
reduce  the  potential  of tube damage due to  corrosion, scaling,  or  erosion.  Carrier assumes  no  responsibility  for 
chiller damage resulting from untreated or improperly treated water. 
5.1.10 - Check relief devices 
Be  sure  that  relief  devices  have  been  piped  to  the  outdoors  in  compliance  with  standard  EN  378-2.  Piping 
connections must allow for access to the valve mechanism for periodic inspection and leak testing. The standard 
19DV relief valves are set to relieve at 500 kPa pressure. 
5.2 Inspect wiring 
WARNING: Do not check the voltage supply without proper equipment and precautions. Serious injury may result. 
Follow power company recommendations. 
 
CAUTION: Do not apply any kind of test voltage, even for a rotation check, if the chiller is under a dehydration 
vacuum. Insulation breakdown and serious damage may result. 
 
1.  Examine the wiring for conformance to the job wiring diagrams and all applicable electrical codes. 
 
2.  Connect a voltmeter across the power wires to the VFD and measure the phase to phase and phase to 
ground voltage. The voltage imbalance for these two measurements should be consistent. If not, confirm 
the power supply to the chiller is a wye configuration with solidly grounded neutral. Compare this reading 
to the voltage rating on the compressor and VFD nameplates. 
 
3.  Compare the ampere rating on the VFD enclosure nameplate to the rating on the compressor nameplate. 
 
4.  The VFD must be wired to components and terminals required for PIC5+ refrigeration control. Check line 
side power and control components shown on the certified prints. 
 
5.  Ensure that fused disconnects or circuit breakers have been supplied to the VFD. 
 
6.  Ensure all electrical equipment and controls are properly grounded in accordance with the job drawings, 
certified drawings, and all applicable electrical codes. 
 
7.  Ensure  the  customer’s  contractor  has  verified  proper  operation  of the pumps,  cooling  tower fans,  and 
associated auxiliary equipment. This includes ensuring motors are properly lubricated and have proper 
electrical supply and proper rotation. The 19DV unit must maintain pump control through the IOBs/Carrier 
Control Panel for freeze prevention algorithm. 
 
8.  Verify  tightness  of  all  wiring  connections  on  the  high  and  low  voltage  terminal  blocks  in  the  VFD 
enclosure. 
 
9.  Inspect the control panels and VFD enclosure to ensure that the contractor has used the knockouts or 
provided top hat to feed the wires into the enclosures. Generally, wiring into the top of the enclosures can 
allow  debris  to  fall  into  the  enclosures.  Clean  and  inspect  the  interior  of  the  power  panel  and  VFD