7.11 Chiller Idle Requirement 
7.11.1 Be idle for a short time: 
There is no special requirement, follow the conventional procedure to check and start-up. 
7.11.2 Be idle for a long time:  
1. Chiller leak prevention  
a. If chiller is idle for one month, suggest running purge every week. 
b. If chiller is idle for more than one month, suggest charging nitrogen into chiller until chiller pressure is 103 kPa 
higher than atmosphere. Before chiller start again, carry out the dehydration process to re-charge refrigerant.  
2.  Need to run the refrigerant pump to avoid potential corrosion. 
3.  Chemically  treated  Water  circulation  through  the  condenser  and  cooler  at  least  once  per  week  for  1-5 
minutes (if they are not drained). 
4.  The  purge  operation  and  refrigerant  pump  operation  should  be  controlled  by  the  PIC  5+  controller  to  au-
tomatically address these items. The water pumps would need to be manually operated by the customer. 
8. PURGE OPERATION SEQUENCE 
 
Refer to fig 53. For the Purge Operation Diagram. 
8.1 Purge Operating Modes 
Purge system has two operation modes: Auto and Manual. 
You can choose it in Configuration Menu->Lab Test Forced->Purge Forced. Select “0” means Auto mode. Select 
“1”  or  “2”  means  Manual  mode,  where  1  means  purge  will  be  active  regardless  the  purge  active  condition,  “2” 
means you can control purge related valves manually. 
8.2 Non-condensable Gas Pump Out 
When purge tank is full of non-condensable gas, the purge compressor inlet temperature drops to -15 °C, so the 
discharge  valve and pump  out  valve  open,  vacuum pump starts  to  pump  out the  non-condensable  gas  inside 
purge tank. 
8.3 Carbon Tank and Regeneration Subsystem 
If the carbon filter is saturated with refrigerant, the heater can heat carbon filter to about 127 °C. The condenser 
valve  and  cooler  valve  is  closed  during  this  time.  Only  the  pump  out  valve  and  regeneration  valve  is  open. 
Meanwhile, the vacuum pump will operate at intervals. Regenerated refrigerant is pumped to cooler. After about 
120 minutes, the regeneration process stops. However, purge system will wait for another 4 hours to let carbon 
filter to cool down before it can operate normally.