97 
 
 
NOTE 1: High leak rates are not acceptable. The necessary steps must be taken to eliminate any leak detected. 
NOTE 2: Fixed refrigerant detectors are not designed to find leaks as they cannot locate the leak. 
9.1.1 Soldering and welding 
Component,  piping  and  connection  soldering  and  welding  operations  must  be  carried  out  using  the  correct 
procedures  and  by  qualified  operators.  Pressurised  containers  must  not  be  subjected  to  shocks,  nor  to  large 
temperature variations during maintenance and repair operations. 
9.1.2 Refrigerant properties 
The  standard  refrigerant  for  the  19DV  chiller  is  HFO  R-1233zd(E).  At  normal  atmospheric  pressure,  HFO  R-
1233zd(E) will boil at 18°C and must, therefore, be kept in pressurized containers or storage tanks. 
The refrigerant is practically odorless when mixed with air and is noncombustible at atmospheric pressure. Read 
the  Material  Safety  Data  Sheet  and  the  latest  standard  EN  378-2  to  learn  more  about  safe  handling  of  this 
refrigerant. 
 
DANGER: HFO R-1233zd(E) in heavy concentrations may displace enough oxygen to cause asphyxiation. When 
handling this refrigerant, protect the hands and eyes and avoid breathing fumes. 
9.1.3 Adding Refrigerant 
 Follow the procedures described in Trim Refrigerant Charge section. 
CAUTION :  Always use the compressor pumpdown function in the PUMPDOWN/LOCKOUT feature to turn on the 
cooler pump and lock out the compressor when transferring refrigerant. Liquid refrigerant may flash into a gas and 
cause possible freeze-up when the chiller pressure is below -53 kPa for HFO R-1233zd(E). 
9.1.4 Adjusting the Refrigerant Charge 
If the addition or removal of refrigerant is required to improve chiller performance, follow the procedures given 
under the Trim Refrigerant Charge section. 
9.1.5 Refrigerant Leak Testing  
Since parts of the refrigerant system operates in vacuum, non-condensables will enter the cooling systems. The 
PIC5+ HMI will issue an alert indicating excessive purge operation. Leaks, which cause frequent purge cycles, 
should be repaired  without delay. Non-condensable gas in the  machine causes higher than normal condenser 
pressure, compressor surge at  start-up  and  frequent purge cycles,  so locate and repair  any leaks as soon  as 
possible. Before making any necessary repairs to a leak, transfer all refrigerant from the vessel. 
9.1.6 Leak Rate 
Carrier recommends that leaks totaling less than the above rate but more than a rate of 0.1% of the total charge 
per year should be repaired during annual maintenance or whenever the refrigerant is transferred for other service 
work. 
9.1.7 Test After Service, Repair, or Major Leak  
If all the refrigerant has been lost or if the chiller has been opened for service, the chiller or the affected vessels 
must be pressure tested and leak tested. Refer to the Leak Test Chiller section to perform a leak test. 
 
WARNING : HFO R-1233zd(E) should not be mixed with air or oxygen and pressurized for leak testing. In general, 
this  refrigerant  should  not  be  present  with  high  concentrations  of  air  or  oxygen  above  atmospheric  pressures, 
because the mixture can undergo combustion. 
9.1.7.1 Testing with refrigerant tracer 
Use an environmentally acceptable refrigerant as a tracer for leak test procedures. Use dry nitrogen to raise the 
machine pressure to leak testing levels. 
9.1.7.2 Testing without refrigerant tracer 
Another  method  of  leak  testing  is  to  pressurize  with  nitrogen  only  and  to  use  a  soap  bubble  solution  or  an 
ultrasonic leak detector to determine if leaks are present. 
9.1.7.3 To pressurize with dry nitrogen  
NOTE: Pressurizing with dry nitrogen for leak testing should not be done if the full refrigerant charge is in the 
vessel because purging the nitrogen is very difficult.