76 
 
 
1 : Expansion valve 
2 : Suction Schrader valve 
 
Note : Clockwise rotation of expansion valve adjustment screw increases the pressure setting and counterclockwise rotation 
decreases pressure setting. 
 
Fig 42 – purge system setting 
 
 
 
5.5 Checking the Installation 
Use the following instructions to verify the condition of the installation: 
1. Turn off, lock out, and tag the input power to the drive. 
2. Wait a minimum of 5 minutes for the DC bus to discharge. 
3. All wiring should be installed in conformance with the applicable local, national, and international codes. 
4. Remove any debris, such as metal shavings from the enclosure. 
5. Check that there is adequate clearance around the machine. 
6.  Verify  that  the  wiring  to  the  terminal  strip  and  the  power  terminals  is  correct  and  that  no  external  voltage 
potential are connected to any of the inputs. 
7. Verify that all of the VFD power module circuit board connectors are fully engaged and taped in place. 
8.  Check  that  the  wire  size  is  within  terminal  specifications  and  that  the  wires  are  tightened  properly  and 
adequately supported. 
9. Check that specified branch circuit protection is installed and correctly rated. 
10. Check that the incoming power is within ±10% of chiller nameplate voltage. 
11. Verify that a properly sized ground wire installed and a suitable earth ground is used. Check for and eliminate 
any grounds between the power leads. Verify that all ground leads are unbroken to the power supply. Only a wye 
secondary power supply transformer with solidly grounded neutral is acceptable as a power supply to this chiller. 
5.6 Check Lubrication Circuit system 
Please check condenser float chamber liquid level. If lubrication system works properly, the liquid level sensor 
should indicate ON.