Any refrigerant transfer and recovery operations must be carried out using a transfer unit for HFO application. A 
connection under the evaporator is supplied with all units for connection to the transfer station. The units must 
never be modified to add refrigerant and oil charging, removal and purging devices. These devices are provided 
with the units. Please see to the certified dimensional drawings for the units. 
2.  INTRODUCTION AND CHILLER FAMILIARISATION 
Prior to initial start-up  of  the 19DV unit,  those  involved in the start-up, operation,  and  maintenance  should be 
thoroughly familiar with these instructions and other necessary job data. This document is outlined so that you 
may become familiar with the control system before performing start-up procedures. Procedures in this manual 
are arranged in the sequence required for proper chiller start-up and operation. 
 
Since 19DV is equipped with VFD (Variable  Frequency Drive), special qualifications are required for personnel 
commissioning these machines or working on the variable-frequency drive. 
2.1 Operating conditions range  
Transport and storage of 19DV units 
The minimum and maximum allowable outside temperatures are: 
Minimum temperature = -15°C 
Maximum temperature = +60°C. 
 
Operating limits 
In operating the minimum and maximum allowable outside temperatures are: 
Minimum temperature = +5°C 
Maximum temperature = +40°C. 
The operating and storage conditions are as those described for the standard machine. The machines must be 
installed inside the building. Electrical cabinets are protected IP23 in accordance with standard IEC60529-1.  
 
The operating range of the selected unit must always be verified at full load and part load by the selection program 
for the chosen configuration. 
The selection program values apply. If they are outside the operating limits below, the selection must be validated 
by the factory customer support team. 
 
Indicative operating range of 19DV chiller 
 
Evaporator entering water temperature 
Evaporator leaving water temperature 
Condenser entering water temperature 
Condenser leaving water temperature 
 
*:  this  minimum  can  be  maintained  with  head  pressure  control  system  such  as  2  or  3  way  valve  or  any  other  applicable 
devices… 
** : In operation or before starting, the user must maintain a water inlet temperature at the evaporator of 28 ° C maximum to 
avoid, in the event of extreme failure of the control system and the pressure switches, any risk of overpressure causing relief 
valve exhaust. 
When chiller is stopped, the maximum permissible circulation temperature in the exchangers is 65 ° C. Higher temperatures can 
result in a risk of valve tripping. 
2.2 Abbreviations and explanations 
Frequently used abbreviations in this manual include: 
 
CCN — Carrier Comfort Network 
CCW — Counter Clock Wise 
CW — Clock Wise 
CHWR — Chilled Water Reclaim 
CHWS — Chilled Water Supply 
ECDW — Entering Condenser Water  
ECW — Entering Chilled Water 
EMS — Energy Management System 
I/O — Input /Output 
IOB — Input /Output Board 
LCDW — Leaving Condenser Water 
LCW — Leaving Chilled Water 
LED — Light-Emitting Diode 
OLTA — Overload Trip Amps 
PIC 5+ — Product Integrated Controls version 5 and more