16 
 
 
In the economizer, due to lower pressure, as liquid enters the high side chamber, some liquid will flash into a 
vapor and cool the remaining liquid. The separated vapor flows to the second stage of the compressor for greater 
cycle efficiency. The second stage guide vane on the compressor acts as a pressure regulating device to stabilize 
operating  conditions.  At  part  load  the  second  stage  guide  vane  will  back  up  gas  flow  and  thereby  raises  the 
economizer pressure to allow appropriate refrigerant flow from economizer to the compressor.  
 
The cooled liquid left in the economizer flows through a low side float valve and then into the evaporator. The float 
valve forms a liquid seal to keep vapor from entering the evaporator. The refrigerant is now at a temperature and 
pressure at which the cycle began. Fig. 4 summarizes the refrigeration cycle. 
The 19DV unit utilizes R-1233zd(E) refrigerant. At atmospheric pressure its boiling point is 18.6°C. The result is 
that at normal operating conditions the evaporator typically will be in a vacuum condition and the condenser will 
operate  at  a  pressure  above  atmospheric  pressure.  Unit  near  room  temperature  will  be  close  to  atmospheric 
pressure.  
 
 
1.Compressor 
2.Condenser 
3.High side float chamber 
4.Low side float chamber 
5.Cooler 
6.Economizer 
Figure 4 – Refrigeration cycle – 19DV Two Stage Compressor 
 
 
 
CAUTION:  To  avoid  adverse  effects  on  chiller  operation,  considerations  must  be  made  to  condenser  water 
temperature control. For steady state operation, the minimum operating refrigerant pressure differential between 
cooler and condenser is approximately 7 psid (48 kPa) with a maximum evaporator refrigerant temperature of 18°C. 
Consult Chiller Builder for required steady state operational limits and low lift options. Inverted start conditions are 
acceptable for short durations of time, but for periods exceeding 5 minutes, a special control solution strategy should 
be  used  to  allow  the  chiller  to  establish  a  minimum  refrigerant  pressure  differential  (and  thereby  adequate 
equipment cooling). 
2.5.5 Refrigerant lubrication cycle 
2.5.5.1 Summary 
The  19DV  Series  chiller  uses  refrigerant  to  lubricate  the  bearings.  The  lubrication  control  is  automatically 
controlled by the chiller controls. In normal RUN mode refrigerant is pumped by means of a refrigerant pump from 
the high side condenser float chamber to the bearings. Prior to start-up liquid level in the high side condenser float 
chamber is maintained by pumping refrigerant liquid from the evaporator to the high side float chamber until level 
sensor is satisfied. 
If liquid high side float level is not satisfied the pump will move refrigerant from the evaporator to the condenser.  
Figures 5 and 6 identify the refrigerant lubrication assembly.