72 
 
 
 
Table 17 – R1233zd(E) Pressure / Temperature 
 
 
5.1.7 Standing Vacuum Test 
When performing the standing vacuum test or chiller dehydration, use a manometer or a wet bulb indicator. Dial 
gages cannot indicate the small amount of acceptable leakage during a short period of time. 
1.  Attach an absolute pressure manometer or wet bulb indicator to the chiller. 
2.  Evacuate the vessel to at least 0.06 kPa [abs], using a vacuum pump. 
3.  Shut off pump valve to hold the vacuum and record the manometer or wet bulb indicator reading. 
4.  If the pressure rise is less than 56 Pa within 8 hours, the chiller is sufficiently tight. 
 
If the pressure rise  exceeds above criteria, re-pressurize the vessel and  conduct leak test  and repair the leak 
point. 
5.1.8- Chiller dehydration 
Dehydration is recommended if the chiller has been open for a considerable period of time, if the chiller is known 
to contain moisture, or if there has been a complete loss of chiller holding charge or refrigerant pressure. 
 
CAUTION: Do not start or megohm-test the compressor motor or any other pump motor, even for a rotation check, 
if the chiller is under dehydration vacuum. Insulation breakdown and severe damage may result. 
 
WARNING: Power to the motor and VFD must be disconnected by an isolation switch before placing the machine 
under a vacuum. To be safe, isolate input power before evacuating the chiller if you are not sure if there are live 
leads to the hermetic motor. 
 
Dehydration can be done at room temperatures. Using a cold trap (Fig. 41) may substantially reduce the time 
required to  complete the dehydration  and is recommended should the  unit be  exposed to liquid moisture. The 
higher the room temperature, the faster dehydration takes place. At low room temperatures, a very deep vacuum 
is  required  for  boiling  off  any  moisture.  If  the  ambient  temperatures  are  low,  contact  a  qualified  service 
representative for the dehydration techniques required.