19 
 
 
1.Compressor 
2.Condenser 
3.Motor cooling system 
4.Moisture indicator 
5.Cooler 
Figure 7 – Motor/VFD cooling system 
 
 
2.5.5.4 VFD cooling 
The VFD enclosure is sealed from the atmosphere to protect electronics from outside contaminants. Refrigerant is 
routed through a coil in the VFD enclosure to regulate enclosure temperature while still maintaining a temperature 
high enough to prevent condensation.  
VFD cooling line is branched off the motor cooling supply. The refrigerant is then drained back into the cooler 
through  the  motor/VFD  drain  line.  The  power  module  of  the  variable-frequency  drive  is  equipped  with  a  heat 
exchanger  to  provide  cooling,  using  the  refrigerant  in  the  machine.  If  equipped  with  a  unit-mounted  VFD,  the 
refrigerant line that feeds the motor cooling also feeds the heat exchanger on the unit-mounted VFD.  
2.5.5.5 VFD  
All  19DV  units  are equipped with a VFD to operate  the  centrifugal hermetic compressor motor. The  VFD  and 
control panel are the main field wiring interfaces for the installing contractor. The VFD and control panel are most 
of time mounted on the chiller. See Manufacturer VFD specific information and VFD schematics.  
This VFD is used with low voltage motors between 380 and 460 vac. It reduces the starting current inrush by 
controlling  the  voltage  and  frequency  to  the  compressor  motor.  Operational  parameters  and  fault  codes  are 
displayed relative to the drive. Refer to specific drive literature along with troubleshooting sections. The display is 
also  the  interface  for  entering  specific  chiller  operational  parameters.  These  parameters  have  been 
preprogrammed at the factory. VFD is designed to operate in an ambient range of up 40°C. 
 
The compressor power variable-frequency drive cabinet includes the following functional components (identified in 
accordance with the references on the wiring diagram):