24 
 
2.5.5.7 Liquid bypass  
The liquid bypass (LBP) system  will  be  an  option for customer when  the  chiller operation envelope has lower 
profile like below: 
 
 
 
 
Fig 12 – liquid bypass envelop 
 
At  very  low  Entering  Condenser  Water  Temp,  the  pressure  difference  between  condenser  and  evaporator  is 
reduced. At bigger system flow rate, the piping resistance may get higher than system pressure difference. In this 
case,  the  liquid  may  stack  in  the  condenser  or  the  economizer,  and  cause  evaporator  lack  of  refrigerant. 
Therefore, the chiller will easily get tripped out due to low evaporating temperature alarm. 
 
The LBP system is designed to avoid above operation failure. It includes an Economizer Bypass Valve installed 
between  condenser float  chamber  and  evaporator  inlet  piping,  an  Economizer  Isolation  Valve  installed  on  the 
vapor piping between economizer and compressor interstage. 
 
When the LBP is activated, the chiller will operate as a single stage system. The condenser float valve will still 
control the system flow rate according to the chamber liquid level. 
 
When  system  lift  decrease,  and  evaporating  saturated  temperature  goes  to  below  evaporator  freezing  point 
(default 0.56°C) for a period of time, or when the Leaving Condenser Water Temperature minus Leaving Evap 
Water Temperature is  less  than  11.8°C  and  Cooler  LTD  is  larger  than  2.78°C  for  a  period  of  time,  the  valve 
installed on bypass piping will be actuated to fully open, and the valve installed on the economizer vapor piping 
needs to be closed completely. 
When the  system  lift  increase,  the  bypassed  line  will  pass  more  refrigerant  than  the  system  requires.  So  the 
evaporator  will  have  too  much  refrigerant,  and  its  liquid  level  will  increase  to  cause  liquid  carryover  to  the 
compressor. The system discharge temperature difference (DTD) will drop down. 
 
When the DTD is less than the required, close the bypass valve and open the economizer vapor line valve, then 
the system will switch back to a two stage economized cycle.