EasyManua.ls Logo

Carrier 19DV Series - Page 36

Carrier 19DV Series
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
* : not available, see official dim drawing
Table 2 19DV dimensions / rigging information
Overall max dimensions
(mm)
Weight max (kg)
Unit
model
heat exch. frame
Compr frame
Motor frame
Power VFD configuration
Length
Height
Width
Rigging
Operating
19DV
G2*G2* (12 feets)
02DV4
B, D,F, or H
VFD LF2 2CC (608 A)
4760
3190
3055
16500
18800
19DV
G2*G2* (12 feets)
02DV4
B, D,F, or H
VFD LF2 4AA (900 A)
4760
3190
3055
17390
19690
19DV
G2*G2* (12 feets)
02DV4
B, D,F, or H
VFD Danfoss E
*
*
*
16700
19000
19DV
G2*G2* (12 feets)
02DV4
B, D,F, or H
Control cabinet only (VFD not unit
mounted)
4760
2900
2585
15070
17370
19DV
G4*G4* (14 feets)
02DV4
B, D,F, or H
VFD LF2 2CC (608 A)
5275
3190
3055
17900
21350
19DV
G4*G4* (14 feets)
02DV4
B, D,F, or H
VFD LF2 4AA (900 A)
5275
3190
3055
18300
21750
19DV
G4*G4* (14 feets)
02DV4
B, D,F, or H
VFD Danfoss E
*
*
*
18100
21550
19DV
G4*G4* (14 feets)
02DV4
B, D,F, or H
Control cabinet only (VFD not unit
mounted)
5275
2900
2585
15970
19420
19DV
H2*H2* (12 feets)
02DV4
B, D,F, or H
VFD LF2 2CC (608 A)
4760
3330
3260
18290
20350
19DV
H2*H2* (12 feets)
02DV4
B, D,F, or H
VFD LF2 4AA (900 A)
4760
3330
3260
18660
20710
19DV
H2*H2* (12 feets)
02DV4
B, D,F, or H
VFD Danfoss E
*
*
*
18470
20530
19DV
H2*H2* (12 feets)
02DV4
B, D,F, or H
Control cabinet only (VFD not unit
mounted)
4760
3075
2790
16480
18610
19DV
H4*H4* (14 feets)
02DV4
B, D,F, or H
VFD LF2 4AA (900 A)
5195
3330
3260
19960
22980
19DV
H4*H4* (14 feets)
02DV4
B, D,F, or H
VFD Danfoss E
*
*
*
19760
22780
19DV
H4*H4* (14 feets)
02DV4
B, D,F, or H
Control cabinet only (VFD not unit
mounted)
5195
3075
2790
17630
20650
COG position (mm)
Rigging chain lengths
(mm)
Unit
model
heat exch. frame
Compr frame
Motor frame
Power VFD configuration
A
B
C
D
E
F
19DV
G2*G2* (12 feets)
02DV4
B, D,F, or H
VFD LF2 2CC (608 A)
1810
1135
1490
2500
2215
2670
19DV
G2*G2* (12 feets)
02DV4
B, D,F, or H
VFD LF2 4AA (900 A)
1800
1270
1470
2500
2150
2720
19DV
G2*G2* (12 feets)
02DV4
B, D,F, or H
VFD Danfoss E
*
*
*
2500
2210
2670
19DV
G2*G2* (12 feets)
02DV4
B, D,F, or H
Control cabinet only (VFD not unit
mounted)
1750
1240
1430
2500
2150
2720
19DV
G4*G4* (14 feets)
02DV4
B, D,F, or H
VFD LF2 2CC (608 A)
2020
1140
1470
2500
2215
2670
19DV
G4*G4* (14 feets)
02DV4
B, D,F, or H
VFD LF2 4AA (900 A)
2000
1270
1475
2500
2150
2720
19DV
G4*G4* (14 feets)
02DV4
B, D,F, or H
VFD Danfoss E
*
*
*
2500
2215
2670
19DV
G4*G4* (14 feets)
02DV4
B, D,F, or H
Control cabinet only (VFD not unit
mounted)
1965
1235
1435
2500
2150
2720
19DV
H2*H2* (12 feets)
02DV4
B, D,F, or H
VFD LF2 2CC (608 A)
1840
1060
1670
2380
2200
2570
19DV
H2*H2* (12 feets)
02DV4
B, D,F, or H
VFD LF2 4AA (900 A)
1820
1210
1690
2390
2110
2630
19DV
H2*H2* (12 feets)
02DV4
B, D,F, or H
VFD Danfoss E
*
*
*
2380
2200
2570
19DV
H2*H2* (12 feets)
02DV4
B, D,F, or H
Control cabinet only (VFD not unit
mounted)
1790
1005
1615
2390
2230
2550
19DV
H4*H4* (14 feets)
02DV4
B, D,F, or H
VFD LF2 4AA (900 A)
1990
1210
1660
2390
2110
2630
19DV
H4*H4* (14 feets)
02DV4
B, D,F, or H
VFD Danfoss E
*
*
*
2380
2200
2570
19DV
H4*H4* (14 feets)
02DV4
B, D,F, or H
Control cabinet only (VFD not unit
mounted)
1980
1015
1590
2380
2230
2550

Table of Contents