42 
 
 
 
1.  Accessory spring isolator 
2.  Soleplate (accessory) attaches securely to isolator 
3.  Level foundation 
4.  Adjusting screws 
Note : Accessory (Carrier supplied, field-installed) soleplate package includes 4. Thickness of grout will 
vary depending on the amount necessary to level chiller.Use only pre-mixed non-shrinkink grout. 
Masterflow 648CP-Plus or Chemrex Embeco 636 Plus Grout 38 to 57 mm thick. 
 
 : Machine foot (side view)  
   : System base (concrete) 
 
Fig 18 – Levelling accessory for 19DV units