21
4.3 - Physical data 30WGA
30WGA 020 025 030 035 040 045 050 060 070 080 090
Operating weight* kg 164 171 171 177 180 185 321 324 332 339 354
Sound levels**
Sound power level 10
-12
W dB(A) 67.0 68.5 69.0 69.3 70.0 70.1 71.5 72.0 72.0 73.0 73.4
Compressors Hermeticscroll48.3r/s
Quantity 1 1 1 1 1 1 2 2 2 2 2
Numberofcapacitysteps 1 1 1 1 1 1 2 2 2 2 2
Minimum capacity % 100 100 100 100 100 100 50 50 50 50 50
Refrigerant R-410A
Oil 160SZ
Charge per compressor l 3 3.3 3.3 3.3 3.3 3.6 3.3 3.3 3.3 3.3 3.6
Control Pro-Dialog+
Evaporator Direct-expansion plate heat exchanger
Water volume l 3.3 3.6 3.6 4.2 4.6 5.0 8.4 9.2 9.6 10.4 12.5
Water connections Victaulic
Inlet/outlet in 1.5 1.5 1.5 1.5 1.5 1.5 2 2 2 2 2
Max.water-sideoperatingpressurewithout
hydronic module
kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Refrigerant connections
Discharge line diameter in 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8
Liquid line diameter in 5/8 5/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8 7/8 7/8
* Weightshownisaguidelineonly.Tondouttheunitrefrigerantcharge,pleaserefertotheunitnameplate
** InaccordancewithISO9614-1,measuredinafreeeld.Thesoundlevelsonlyapplytounitswithoutoptions.Declareddualnumbernoiseemissionvaluesinaccordance
withISO4871(withanassociateduncertaintyof+/-3dB(A)).
4.4 - Physical data 61WG/30WG/30WGA units with hydronic module
61WG/30WG/30WGA 020 025 030 035 040 045 050 060 070 080 090
Operating weight 30WG/61WG (option 116V + 270V)* kg 305 313 313 321 327 334 513 521 533 544 574
Weight 30WGA (option 116V)* kg 250 258 258 263 266 271 431 435 442 449 465
Height** mm 1463 1463 1463 1463 1463 1463 1463 1463 1463 1463 1463
Hydronic module with option 293 or 293A
Maximum operating pressure kPa 300 300 300 300 300 300 300 300 300 300 300
Waterlter(max.removedparticlediameter) mm 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
Expansion tank capacity*** l 8 8 8 8 8 8 12 12 12 12 12
Water connections in 1.5 1.5 1.5 1.5 1.5 1.5 2 2 2 2 2
* Weightshownisaguidelineonly..
** Thelengthandwidthdimensionsarethesameasforthestandardunit.
*** Whendelivered,thestandardpre-inationofthetanksisnotnecessarytheoptimalvalueforthesystem.Topermitchangingthewatervolume,changetheination
pressuretoapressurethatisclosetothestaticheadofthesystem.Fillthesystemwithwater(purgingtheair)toapressurevaluethatis10to20kPahigherthanthe
pressureinthetank.