5.15 - Plate heat exchanger pressure drop (includes internal piping)
Evaporator - standard unit without hydronic module - Water only
61WG/30WG/30WGA 020-045 61WG/30WG/30WGA 050-090
1 61WG/30WG/30WGA020
2 61WG/30WG/30WGA025to61WG/30WG/30WGA030
3 61WG/30WG/30WGA035
4 61WG/30WG/30WGA040
5 61WG/30WG/30WGA045
6 61WG/30WG/30WGA050
7 61WG/30WG/30WGA060
8 61WG/30WG/30WGA070
9 61WG/30WG/30WGA080
10 61WG/30WG/30WGA090
Condenser - standard unit without hydronic module - Water only
61WG/30WG 020-045
1 61WG/30WG020
2 61WG/30WG025to61WG/30WG030
3 61WG/30WG035
4 61WG/30WG040
5 61WG/30WG045
6 61WG/30WG050
7 61WG/30WG060
8 61WG/30WG070
9 61WG/30WG080
10 61WG/30WG090
61WG/30WG 050-090
Pressure drop, kPa
Waterowrate,l/s
Pressure drop, kPa
Waterowrate,l/s
Pressure drop, kPa
Waterowrate,l/s
Pressure drop, kPa
Waterowrate,l/s
5.14 - Protection against cavitation (option 116)
To ensure the durability of the pumps in the integrated
hydronic modules, the control algorithm of the 61WG/30WG/
30WGA units incorporates anti-cavitation protection.
It is therefore necessary to ensure a minimum pump entering
pressure of 60 kPa (0.6 bar) during operation and at shut-down.
A pressure below 60 kPa will prohibit unit start-up or cause
an alarm with the unit shutting down.
In order to obtain sufcient pressure, it is recommended:
• to pressurise the hydronic circuit between 100 kPa and
300 kPa (1 and 3 bar) maximum on the suction side of
the pump,
• to clean the hydronic circuit before charging water,
• to regularly clean the screen lter.