4.5 - Electrical data 61WG/30WG/30WGA
61WG without hydronic module 020 025 030 035 040 045 050 060 070 080 090
Power circuit
Nominal voltage V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply 24 V, via internal transformer
Maximum start-up current draw (Un)*
Standard unit A 98 142 142 147 158 197 161 163 172 185 226
Unit with electronic starter option A 53.9 78.1 78.1 80.9 86.9 108.4 98 99 105 114 139
Unit power factor at maximum capacity** 0.83 0.82 0.84 0.83 0.82 0.84 0.82 0.82 0.83 0.82 0.84
Maximum operating power input** kW 9.7 11.4 12.8 14.7 16.6 18.7 22.8 25.6 29.4 33.2 37.4
Nominal unit operating current draw*** A 12.9 15.8 16.8 19.2 20.7 24.6 31.6 33.6 38.4 41.4 49.2
Maximum operating current draw (Un)**** A 16.1 19.6 21.1 24.4 26.7 30.9 39.2 42.2 48.8 53.4 61.8
Maximum operating current draw (Un-10%)† A 17.8 21.6 23.2 26.9 29.4 34.0 43.2 46.4 53.8 58.8 68.0
Customer-side unit power reserve Customer reserve at the 24 V control power circuit
Short-circuit stability and protection Seetablebelow"Short-circuitstabilitycurrent"
*Maximuminstantaneousstart-upcurrentatoperatinglimitvalues(maximumoperatingcurrentofthesmallestcompressor(s)+lockedrotorcurrentorlimitedstart-upcurrentofthelargestcompressor).
**Maximumpowerinputattheunitoperatinglimits.
***ValuesobtainedatstandardisedEuroventconditions:evaporatorentering/leavingwatertemperature10°C/7°C,condenserentering/leavingwatertemperature30°C/35°C.
****Maximumunitoperatingcurrentatmaximumunitpowerinputand400V.
†Maximumunitoperatingcurrentatmaximumunitpowerinputand360V.
30WG without hydronic module 020 025 030 035 040 045 050 060 070 080 090
Power circuit
Nominal voltage V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply 24 V, via internal transformer
Maximum start-up current draw (Un)*
Standard unit A 98 142 142 147 158 197 161 163 172 185 227
Unit with electronic starter option A 53.9 78.1 78.1 80.9 86.9 108.4 96.8 97.9 104.1 112.3 137.4
Unit power factor at maximum capacity** 0.83 0.82 0.84 0.83 0.82 0.84 0.82 0.82 0.83 0.82 0.84
Maximum operating power input** kW 9.7 11.4 12.8 14.7 16.6 18.7 22.8 24.6 29.4 33.2 37.4
Nominal unit operating current draw*** A 12.9 18.8 16.8 19.2 20.7 24.6 31.6 33.6 38.4 41.4 49.2
Maximum operating current draw (Un)**** A 15.6 18.7 19.8 23.2 25.4 29.0 37.5 39.6 46.4 50.8 58.0
Maximum operating current draw (Un-10%)† A 17.2 20.6 21.8 25.6 28.0 31.9 41.2 43.6 51.2 56.0 63.8
Customer-side unit power reserve Customer reserve at the 24 V control power circuit
Short-circuit stability and protection Seetablebelow"Short-circuitstabilitycurrent"
*Maximuminstantaneousstart-upcurrentatoperatinglimitvalues(maximumoperatingcurrentofthesmallestcompressor(s)+lockedrotorcurrentorlimitedstart-upcurrentofthelargestcompressor).
**Maximumpowerinputattheunitoperatinglimits.
***ValuesobtainedatstandardisedEuroventconditions:evaporatorentering/leavingwatertemperature12°C/7°C,condenserentering/leavingwatertemperature30°C/35°C.
****Maximumunitoperatingcurrentatmaximumunitpowerinputand400V.
†Maximumunitoperatingcurrentatmaximumunitpowerinputand360V.
30WGA without hydronic module 020 025 030 035 040 045 050 060 070 080 090
Power circuit
Nominal voltage V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply 24 V, via internal transformer
Maximum start-up current draw (Un)*
Standard unit A 98 142 142 147 158 197 161 163 172 185 228
Unit with electronic starter option A 53.9 78.1 78.1 80.9 86.9 108.4 96.8 97.9 104.1 112.3 137.4
Unit power factor at maximum capacity** 0.83 0.82 0.84 0.83 0.82 0.84 0.82 0.82 0.83 0.82 0.84
Maximum operating power input** kW 9.7 11.4 12.8 14.7 16.6 18.7 22.8 25.6 29.4 33.2 37.4
Nominal unit operating current draw*** A 11.4 13.8 14.7 16.5 18.1 21.2 27.6 29.4 33.0 36.2 42.4
Maximum operating current draw (Un)**** A 14.7 17.7 19.3 21.7 24.1 27.5 35.4 38.7 43.5 48.1 55.0
Maximum operating current draw (Un-10%)† A 16.2 19.5 21.3 23.9 26.5 30.3 39.0 42.6 47.8 53.0 60.6
Customer-side unit power reserve Customer reserve at the 24 V control power circuit
Short-circuit stability and protection Seetablebelow"Short-circuitstabilitycurrent"
*Maximuminstantaneousstart-upcurrentatoperatinglimitvalues(maximumoperatingcurrentofthesmallestcompressor(s)+lockedrotorcurrentorlimitedstart-upcurrentofthelargestcompressor).
**Maximumpowerinputattheunitoperatinglimits.
***Valuesobtainedatthefollowingconditions:evaporatorentering/leavingwatertemperature12°C/7°C,condenserentering/leavingwatertemperature45°C.
****Maximumunitoperatingcurrentatmaximumunitpowerinputand400V.
†Maximumunitoperatingcurrentatmaximumunitpowerinputand360V.
4.6 - Short-circuit stability current (TN system*) - standard unit (with main disconnect switch)
61WG/30WG/30WGA 020 025 030 035 040 045 050 060 070 080 090
Value with non-specied upstream protection
Short-termcurrentat1s-Icw-kArms 3 3 3 3 3 3 3 3 3 3 3
Admissiblepeakcurrent-Ipk-kApk 6 6 6 6 6 6 6 6 6 6 6
Maximum value with upstream protection (by circuit breaker)
Conditionalshort-circuitcurrentIcc-kArms 40 40 40 40 40 40 40 40 40 40 40
Schneidercircuitbreaker-Compactseries NSX 100N
Referencenumber** LV429795
* Earthing system type
** Ifanother current limitation protection system is used, its time-current and thermal constraint (I²t) trip characteristicsmust be at least equivalent to those of the
recommendedSchneidercircuitbreaker.ContactyournearestCarrierofce.
Theshort-circuitstabilitycurrentvaluesaboveareinaccordancewiththeTNsystem.