44
16.4 - Oil charge adjustment
If a suction riser is used, the oil charge must be adjusted. Add
the equivalent volume to half of the lower part of each siphon
trap (see gure below), when the unit is empty.
Oil volume for a siphon trap
16.5 - Operation of two units in master/slave mode
(option 58)
The control of a master/slave assembly is in the entering
water piping (system return). All parameters, required for
the master/slave function must be configured using the
Service Conguration menu.
All remote controls of the master/slave assembly (start/stop,
set point, load shedding etc.) are controlled by the unit
congured as master and must only be applied to the master
unit.
IMPORTANT: To permit master/slave operation both units
must be equipped with option 58.
Depending on the installation and control type, each unit can
control its own water pump.
16.6 - Parallel or serial connection of two 61WG/30WG/
30WGA units
Entering water control for a hydronic kit
1
2
Legend
1 Master unit
2 Slave unit
AdditionalCCNboard(oneperunit,withconnectionviacommunicationbus)
Controlboxesofthemasterandslaveunits
Waterinlet(forcustomerswithbothunits)
Wateroutlet(forcustomerswithbothunits)
Water pumps for each unit (included as standard for units with hydronic module)
Additionalsensorsforleavingwatercontrol,tobeconnectedtochannel1of
theslaveboardsofeachmasterandslaveunit
CCNcommunicationbus
Connection of two additional sensors
17 - MAJOR SYSTEM COMPONENTS AND OPERATION
DATA
17.1 - Compressors
61WG/30WG/30WGA units use hermetic scroll compressors.
The only refrigerant permitted for these compressors is
R-410A.
30WGA split units operating with an air-cooled condenser,
are supplied with the refrigerant circuit and consequently
the compressor under nitrogen pressure of 100 kPa (1 bar).
The compressors are not certied for mobile applications or
use in explosive environments.
For more information contact the Carrier service team for
maintenance instructions.
IMPORTANT: All compressor and system pressure tests
must be carried out by qualied personnel, taking the greatest
care with potential dangers resulting from the pressures
used, and respecting the maximum operating pressure limit
on the high and low-pressure side, shown on the unit and
compressor name plates.
• • Maximum operating pressure, low-pressure side
(61WG/30WG/30WGA): 2820 kPa (28.2 bar)
• • Maximum operating pressure, high-pressure side
(61WG/30WG): 4870 kPa (48.7 bar).
• • Maximum operating pressure, high-pressure side
(30WGA): 4170 kPa (41,7 bars)
•
These setpoint must be observed for 30WGA split units using
an air-cooled condenser, when the installer checks the
complete system leak tightness.
1
2
Leaving water control
Seelegendinthenextcolumn.