39
11.4 - Pump curve (units with hydronic modules)
Data applicable for:
- Fresh water 20 °C
- In case of use of the glycol, the maximum water ow is
reduced
- The curves represented below are in normal conditions:
leaving water on the back side of the unit (without option
274).
11.4.1 - Low pressure pumps 61WG/30WG/30WGA
(options 116T - 270T)
11.4.2 - High pressure pumps 61WG/30WG/30WGA
(options 116V - 270V)
Pressure head, kPa
Waterowrate,l/s
1 61WG/30WG/30WGA020-080
2 61WG/30WG/30WGA090
3 61WG/30WG/30WGA020-045
4 61WG/30WG/30WGA050-090
Waterowrate,l/s
12 - OPERATION OF 61WG UNITS WITH SPECIFIC
HEATING CONTROL (OPTION 153)
12.1 - Operating principle
61WG units are specially designed to optimise the operation
of heating installations that require hot-water production for
a traditional heating system and domestic hot-water
production.
The Pro-Dialog+ control system of the 61WG units includes
algorithms that permit constant automatic optimisation of:
• control of a directional on/off three-way valve based on
the heating or domestic hot water requirements
• control of the electric heating stages allowing relief of
the heating loop
• hot-water setpoint reset (heating application) based on
the air temperature
• priority control between heating application and
domestic hot-water application.
NOTE: The installer is responsible for ensuring that the
installation complies with the applicable legislation in
terms of electrical and thermal safety.
12.2 - Auxiliary electronic board (AUX1) - analogue and
digital inputs and outputs
R S V
CH
4
J7
CH
1
--
R S V
--
J2
--
CH13
CH
3
J4
CH
2
--
-- G +
CH
10
--
J5
T
P
V
CH14
3 2 1
--
3 2 1
CH
8
--
-- G +
CH
7
--
J6
CH14
CH
6
--
J8
CH
5
CH
9
• Connector J2: Digital outputs CH 1 to 4 for fan stages
1 to 4.
• Connector J3: Digital output CH 6 to control a directional
on/off three-way valve
• Connector J6: Analogue input CH 11 for outside air
temperature sensors
• Connector J6: Analogue input CH 12 for information
on domestic hot water demand
• Connector J7: Analogue input CH 13 for information
on domestic hot water demand
• Connector J8: Analogue input CH 14 for information
on summer operation only (domestic hot water only)
To apply the different congurations required, refer to the
instructions in the Pro-Dialog+ Control IOM.