23
4.7 - Electrical data, optional hydronic module
The pumps that are factory-installed in these units comply with the European Ecodesign directive ErP. The additional
electrical data required* is as follows:
Motors of xed-speed hydronic module pumps, 61WG/30WG/30WGA (options 116T and 270T)
No.** Description*** 61WG/30WG/30WGA - options 116T and 270T (low-pressure pumps)
20 25 30 35 40 45 50 60 70 80 90
1 Nominalefciencyatfullloadandnominalvoltage % 81,1 81,1 81,1 81,1 81,1 81,1 81,1 81,1 81,1 81,1 83,4
1 Nominalefciencyat75%ratedloadandnominalvoltage % 80,8 80,8 80,8 80,8 80,8 80,8 80,8 80,8 80,8 80,8 81,2
1 Nominalefciencyat50%ratedloadandnominalvoltage % 77,5 77,5 77,5 77,5 77,5 77,5 77,5 77,5 77,5 77,5 78,3
2 Efciencylevel IE3
3 Year of manufacture This information varies depending on the manufacturer and model at the time of
incorporation.Pleaserefertothemotornameplates.
4 Manufacturer's name and trademark, commercial registration
numberandplaceofmanufacturer
5 Product'smodelnumber
6 Numberofmotorpoles 2 2 2 2 2 2 2 2 2 2 2
7-1 Rated shaft power output at full load and nominal voltage (400 V) kW 0,8 0,8 0,8 0,8 0,8 0,8 0,8 0,8 0,8 0,8 1,3
7-2 Maximum power input (400 V)**** kW 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,6
8 Rated input frequency Hz 50 50 50 50 50 50 50 50 50 50 50
9-1 Rated voltage V 3x400
9-2 Maximum current drawn (400 V)† A 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,9
10 Rated speed rpm 2850 2850 2850 2850 2850 2850 2850 2850 2850 2850 2890
r/s 47 47 47 47 47 47 47 47 47 47 48
11 Productdisassembly,recyclingordisposalatendoflife Disassemblyusingstandardtools.Disposalandrecyclingusinganappropriate
company.
12 Operatingconditionsforwhichthemotorisspecicallydesigned
I -Altitudesabovesealevel m < 1000††
II -Ambientairtemperature °C < 40
IV-Maximumairtemperature Pleaserefertotheoperatingconditionsgiveninthismanualorinthespecicconditions
intheCarrierselectionprograms.
V - Potentially explosive atmospheres Non-ATEX environment
Motors of variable-speed hydronic module pumps, 61WG/30WG/30WGA (options 116V and 270V)
No.** Description*** 61WG/30WG/30WGA - options 116V and 270V (high-pressure pumps)
20 25 30 35 40 45 50 60 70 80 90
1 Nominalefciencyatfullloadandnominalvoltage % 83,4 83,4 83,4 83,4 83,4 83,4 84,8 84,8 84,8 84,8 84,8
1 Nominalefciencyat75%ratedloadandnominalvoltage % 81,2 81,2 81,2 81,2 81,2 81,2 82,2 82,2 82,2 82,2 82,2
1 Nominalefciencyat50%ratedloadandnominalvoltage % 78,3 78,3 78,3 78,3 78,3 78,3 79 79 79 79 79
2 Efciencylevel IE3
3 Year of manufacture This information varies depending on the manufacturer and model at the time of
incorporation.Pleaserefertothemotornameplates.
4 Manufacturer's name and trademark, commercial registration
numberandplaceofmanufacturer
5 Product'smodelnumber
6 Numberofmotorpoles 2 2 2 2 2 2 2 2 2 2 2
7-1 Rated shaft power output at full load and nominal voltage (400 V) kW 1,3 1,3 1,3 1,3 1,3 1,3 1,7 1,7 1,7 1,7 1,7
7-2 Maximum power input (400 V)**** kW 1,6 1,6 1,6 1,6 1,6 1,6 2,4 2,4 2,4 2,4 2,4
8 Rated input frequency Hz 50 50 50 50 50 50 50 50 50 50 50
9-1 Rated voltage V
3x400 3x400 3x400 3x400 3x400 3x400 3x4003x400 3x400 3x400 3x400
9-2 Maximum current drawn (400 V)† A 2,9 2,9 2,9 2,9 2,9 2,9 4,2 4,2 4,2 4,2 4,2
10 Rated speed rpm 2890 2890 2890 2890 2890 2890 2870 2870 2870 2870 2870
r/s 48 48 48 48 48 48 48 48 48 48 48
11 Productdisassembly,recyclingordisposalatendoflife Disassemblyusingstandardtools.Disposalandrecyclingusinganappropriate
company.
12 Operatingconditionsforwhichthemotorisspecicallydesigned
I -Altitudesabovesealevel m < 1000††
II -Ambientairtemperature °C < 40
IV-Maximumairtemperature Pleaserefertotheoperatingconditionsgiveninthismanualorinthespecicconditions
intheCarrierselectionprograms.
V - Potentially explosive atmospheres Non-ATEX environment
* Requiredbyregulation640/2009withregardtotheapplicationofdirective2009/125/EContheeco-designrequirementsforelectricmotors
** Itemnumberimposedbyregulation640/2009,annexI2b.
*** Descriptiongivenbyregulation640/2009,annexI2b.
**** Toobtainthemaximumpowerinputforaunitwithhydronicmoduleaddthemaximumunitpowerinputfromtheelectricaldatatabletothepumppowerinput.
† Toobtainthemaximumunitoperatingcurrentdrawforaunitwithhydronicmoduleaddthemaximumunitcurrentdrawfromtheelectricaldatatabletothepumpcurrent
draw.
†† Above1000m,adegradationof3%foreach500mshouldbetakenintoconsideration.